Hydro Potential from Catchment Rainfall: Flow, Power and Energy

Mean river flow from catchment area, rainfall and runoff coefficient, and the mean power, annual energy and capacity factor of a hydro plant using it.

Thermal power plant

Inputs

Examples: 500 km2, 1,200 mm, runoff 0.6, 80 % used, 80 m, 85 %, 80 MWHimalayan 2,000 km2, 1,800 mm, 0.7, 60 %, 250 m, 88 %, 300 MWSmall stream 25 km2, 900 mm, 0.4, 70 %, 40 m, 80 %, 1 MW

Accepted: 0.01 to 1,000,000 km²
Accepted: 50 to 10,000 mm
Accepted: 5 to 100 %
Accepted: 5 to 100 %
Accepted: 1 to 2,000 m
Accepted: 50 to 100 %
Accepted: 0.001 to 10,000 MW
Accepted: 990 to 1,030 kg/m³

Results

A yearly average; seasonal flow and the flow-duration curve decide how much of it a plant of given size can actually use without storage.

Annual runoff9,000,000m³
Mean flow used0.19963m³/s
Mean power0.062648MW
Annual energy0.54917GWh
Capacity factor6.2648%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 500 km2, 1,200 mm, runoff 0.6, 80 % used, 80 m, 85 %, 80 MW. The inputs, in the units selected above:

InputValue
Catchment area500.00 km²
Mean annual rainfall1,200.0 mm
Runoff coefficient (share reaching the river)60.000 %
Share of the runoff used by the plant80.000 %
Net head80.000 m
Overall efficiency85.000 %
Installed capacity80.000 MW
Water density1,000.0 kg/m³

Applying the formula below gives:

ResultValue
Annual runoff3.6000e+08 m³
Mean flow used9.1262 m³/s
Mean power6.0858 MW
Annual energy53.348 GWh
Capacity factor7.6073 %

Open this example in the calculator and change any input.

Formula

\(V = ARC, \quad \bar Q = \frac{Vf_u}{t_{yr}}, \quad \bar P = \rho g\bar QH\eta_o, \quad E = \bar Pt_{yr}\)

Variables

Symbol Meaning SI unit
\(A\) Catchment area m²
\(R\) Mean annual rainfall m
\(C\) Runoff coefficient (share reaching the river) -
\(f_u\) Share of the runoff used by the plant -
\(H\) Net head m
\(\eta_o\) Overall efficiency -
\(P_{inst}\) Installed capacity W
\(\rho\) Water density kg/m³
\(V\) Annual runoff m³
\(\bar Q\) Mean flow used m³/s
\(\bar P\) Mean power W
\(E\) Annual energy J
\(CF\) Capacity factor -

Method and standards

Annual water balance of a catchment.

Where it is used

  • Pre-feasibility screening of hydro sites.
  • Checking claimed annual generation.

Common mistakes

  • Mixing catchment area in km² with rainfall in mm without converting.
  • Assuming all runoff can be used.

Assumptions and limits

  • Annual averages; no evaporation from reservoirs beyond the runoff coefficient.

Questions and answers

What runoff coefficient should I use?

From gauged flows if they exist; otherwise 0.2–0.4 for flat cultivated land, 0.5–0.7 for hilly or forested catchments and up to 0.9 for rocky or urban ones.

Why is the capacity factor low for run-of-river plants?

Monsoon floods exceed the turbine capacity and dry-season flows fall well below it, so much of the runoff is either spilled or produces part-load output.

What do the defaults represent?

A 500 km² catchment with 1,200 mm rain, 60 % runoff and 80 % used, 80 m head, 85 % efficiency and 80 MW installed: about 9.1 m³/s, 6.1 MW mean and 53 GWh a year (capacity factor 7.6 %).

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Nag, Power Plant Engineering, 3rd ed. (Tata McGraw-Hill, 2008), ch. 10 (hydrology: rainfall, run-off and power potential)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.