Worked example
Example: 30 t/h exhaust at 450 °C to 160 °C, 11 bar. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Exhaust gas flow | 30,000 kg/h |
| Gas specific heat | 1.1000 kJ/(kg·K) |
| Exhaust temperature | 450.00 °C |
| Lowest allowed exit temperature (dew point margin) | 160.00 °C |
| Steam pressure (absolute) | 11.000 bar |
| Feedwater temperature | 105.00 °C |
| Efficiency of the boiler it displaces | 85.000 % |
| Fuel cost per GJ (same calorific basis as the efficiency) | 500.00 - |
| Operating hours per year | 8,000.0 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat recoverable | 2,658.3 kW |
| Steam raised (upper bound: pinch ignored) | 4,090.2 kg/h |
| Fuel heat saved | 3,127.5 kW |
| Annual fuel cost saved | 4.5035e+07 |
Open this example in the calculator and change any input.
Formula
\(Q = \dot m_gc_p(T_1 - T_2), \quad \dot m_s \le \frac{Q}{h_g - h_{fw}}, \quad \dot Q_f = \frac{Q}{\eta_b}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_g\) | Exhaust gas flow | kg/s |
| \(c_p\) | Gas specific heat | J/(kg·K) |
| \(T_1\) | Exhaust temperature | K |
| \(T_2\) | Lowest allowed exit temperature (dew point margin) | K |
| \(p_s\) | Steam pressure (absolute) | Pa |
| \(T_{fw}\) | Feedwater temperature | K |
| \(\eta_b\) | Efficiency of the boiler it displaces | - |
| \(c_f\) | Fuel cost per GJ | - |
| \(t\) | Operating hours per year | s |
| \(Q\) | Heat recoverable | W |
| \(\dot m_s\) | Steam raised (upper bound: pinch ignored) | kg/s |
| \(\dot Q_f\) | Fuel heat saved | W |
| \(C\) | Annual fuel cost saved | - |
Method and standards
Energy balances: the heat given up by the gas between the two temperatures; the steam it could raise from compressed feedwater at the steam pressure to dry saturated steam (IAPWS-IF97); and the fuel heat a boiler of the given efficiency would burn for the same heat, costed per GJ.
Where it is used
- Screening heat recovery projects on kilns, furnaces and engines.
Common mistakes
- Cooling below the dew point.
- Ignoring the pinch.
Assumptions and limits
- Constant gas specific heat.
- The steam figure uses all the heat down to the exit limit, even below the saturation temperature plus pinch, so it is an upper bound; the HRSG calculator gives the real split.
- The fuel cost per GJ and the boiler efficiency must be on the same calorific basis (both gross or both net).
References
- Energy balances (definitions)
- Steam and water properties from IAPWS-IF97
Questions and answers
What limits the exit temperature?
The acid or water dew point for sulphur-bearing or wet gases, and the pinch for steam generation.
Why divide by boiler efficiency?
Recovered heat displaces fuel that a boiler would burn at that efficiency.
Is the steam figure exact?
No, it is an upper bound; the pinch usually lowers it.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.