Absorption Chilling from Exhaust or Hot Water

Cooling from waste heat in a single- or double-effect absorption chiller, heat to the cooling tower, and the electric chiller power and cost it avoids.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalChemical and fertiliserFood, dairy and textileAir conditioning and chillers

Inputs

Examples: 1 MW hot water, single-effect2 MW exhaust, double-effect

Leave 0 to ignore; it is subtracted from the electricity the absorption chiller saves.

Results

Absorption chillers reject the driving heat as well as the cooling: the cooling tower duty is about 1.6 times that of an electric chiller here.

The absorption plant's own pumps and the larger cooling tower's fans and pumps are not deducted; enter them to get the net saving.

Cooling capacity2,400.0kW
Cooling capacity in tons of refrigeration682.43
Heat to the cooling tower4,400.0kW
Electric chiller power avoided400.00kW
Annual electricity saving1.9200e+07

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 MW hot water, single-effect. The inputs, in the units selected above:

InputValue
Driving heat delivered to the chiller1,000.0 kW
Absorption chiller COPSingle-effect (0.7)
Electric chiller COP (for comparison)5.5000 -
Electricity price per kWh8.0000 -
Absorption plant's own electricity (pumps, extra tower fans and pumps)0 kW
Hours per year6,000.0 h

Applying the formula below gives:

ResultValue
Cooling capacity700.00 kW
Cooling capacity in tons of refrigeration199.04
Heat to the cooling tower1,700.0 kW
Electric chiller power avoided127.27 kW
Annual electricity saving6,109,091

Open this example in the calculator and change any input.

Formula

\(Q_c = COP\cdot Q_h, \quad Q_r = Q_h + Q_c, \quad P_{el} = \frac{Q_c}{COP_e}, \quad S = (P_{el} - P_{aux})\,t\,c_e\)

Variables

Symbol Meaning SI unit
\(Q_h\) Driving heat delivered to the chiller W
\(COP\) Absorption chiller COP -
\(COP_e\) Electric chiller COP (for comparison) -
\(c_e\) Electricity price per kWh -
\(t\) Hours per year s
\(Q_c\) Cooling capacity W
\(Q_r\) Heat to the cooling tower W
\(P_{el}\) Electric chiller power avoided W
\(P_{aux}\) absorption plant's own electricity (pumps, extra tower fans and pumps) W
\(S\) Annual electricity saving -

Method and standards

Chiller energy balance.

Where it is used

  • Trigeneration studies.

Common mistakes

  • Using the double-effect COP with low-grade heat.
  • Ignoring cooling tower pumping.

Assumptions and limits

  • Rated COPs; part load differs. The COP choices are typical rated values for single- and double-effect machines; use the maker's figure for a real machine.
  • The saving is net of the absorption plant's own electricity only when that is entered.

References

  • Energy balances (definitions); 1 ton of refrigeration = 3.516 853 kW

Questions and answers

What drives a single-effect chiller?

Hot water at 85–95 °C or low-pressure steam; double-effect needs about 170 °C or exhaust.

Why is the cooling tower bigger?

It rejects the driving heat as well as the cooling load.

When does it pay?

When the waste heat is free and electricity is expensive.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.