Worked example
Example: 1 MW hot water, single-effect. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Driving heat delivered to the chiller | 1,000.0 kW |
| Absorption chiller COP | Single-effect (0.7) |
| Electric chiller COP (for comparison) | 5.5000 - |
| Electricity price per kWh | 8.0000 - |
| Absorption plant's own electricity (pumps, extra tower fans and pumps) | 0 kW |
| Hours per year | 6,000.0 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Cooling capacity | 700.00 kW |
| Cooling capacity in tons of refrigeration | 199.04 |
| Heat to the cooling tower | 1,700.0 kW |
| Electric chiller power avoided | 127.27 kW |
| Annual electricity saving | 6,109,091 |
Open this example in the calculator and change any input.
Formula
\(Q_c = COP\cdot Q_h, \quad Q_r = Q_h + Q_c, \quad P_{el} = \frac{Q_c}{COP_e}, \quad S = (P_{el} - P_{aux})\,t\,c_e\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_h\) | Driving heat delivered to the chiller | W |
| \(COP\) | Absorption chiller COP | - |
| \(COP_e\) | Electric chiller COP (for comparison) | - |
| \(c_e\) | Electricity price per kWh | - |
| \(t\) | Hours per year | s |
| \(Q_c\) | Cooling capacity | W |
| \(Q_r\) | Heat to the cooling tower | W |
| \(P_{el}\) | Electric chiller power avoided | W |
| \(P_{aux}\) | absorption plant's own electricity (pumps, extra tower fans and pumps) | W |
| \(S\) | Annual electricity saving | - |
Method and standards
Chiller energy balance.
Where it is used
- Trigeneration studies.
Common mistakes
- Using the double-effect COP with low-grade heat.
- Ignoring cooling tower pumping.
Assumptions and limits
- Rated COPs; part load differs. The COP choices are typical rated values for single- and double-effect machines; use the maker's figure for a real machine.
- The saving is net of the absorption plant's own electricity only when that is entered.
References
- Energy balances (definitions); 1 ton of refrigeration = 3.516 853 kW
Questions and answers
What drives a single-effect chiller?
Hot water at 85–95 °C or low-pressure steam; double-effect needs about 170 °C or exhaust.
Why is the cooling tower bigger?
It rejects the driving heat as well as the cooling load.
When does it pay?
When the waste heat is free and electricity is expensive.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.