FireCADCalc

Air Compressor Heat Recovery to Water

Heat recoverable from an air compressor's oil and air coolers as hot water, the water flow for a temperature rise, and the fuel and cost it saves.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalChemical and fertiliserFood, dairy and textileAir compressor and receiver

Inputs

Examples: 250 kW screw, 75 %, 40 K riseTwo 160 kW, 80 %, 30 K

Per GJ on the same calorific basis (GCV or NCV) as the heater efficiency.

Results

Almost all compressor power becomes heat; oil-injected screw compressors let 70–80 % be recovered as water at 60–80 °C.

Heat recovered256.00kW
Water heated7.3373t/h
Annual fuel cost saved3,252,706

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 250 kW screw, 75 %, 40 K rise. The inputs, in the units selected above:

InputValue
Compressor shaft power250.00 kW
Share of shaft power recoverable75.000 %
Water temperature rise40.000 K
Efficiency of the heater it replaces (same GCV or NCV basis as the fuel cost)85.000 %
Fuel cost per GJ of fuel heat500.00 -
Loaded hours per year6,000.0 h

Applying the formula below gives:

ResultValue
Heat recovered187.50 kW
Water heated4.0305 t/h
Annual fuel cost saved2,382,353

Open this example in the calculator and change any input.

Formula

\(Q = f_rP, \quad \dot m_w = \frac{Q}{c_w\Delta T_w}, \quad C = \frac{Q}{\eta_b}t\,c_f\)

Variables

Symbol Meaning SI unit
\(P\) Compressor shaft power W
\(f_r\) Share of shaft power recoverable -
\(\Delta T_w\) Water temperature rise K
\(\eta_b\) Efficiency of the heater it replaces -
\(c_f\) Fuel cost per GJ, on the same GCV or NCV basis as \(\eta_b\) -
\(c_w\) specific heat of water, 4186.8 J/(kg·K)
\(t\) Loaded hours per year s
\(Q\) Heat recovered W
\(\dot m_w\) Water heated kg/s
\(C\) Annual fuel cost saved -

Method and standards

Energy balance.

Where it is used

  • Compressor house energy projects.

Common mistakes

  • Counting unloaded hours.
  • No dump cooler for when heat is not needed.

Assumptions and limits

  • Water c_p 4.1868 kJ/(kg·K).
  • The recovered heat is assumed to be used in full during every loaded hour; if the hot-water demand is smaller or not coincident, the saving is smaller.

References

  • Energy balances (definitions)

Questions and answers

Why can so much be recovered?

Nearly all the shaft power ends up as heat in the oil and air coolers.

What water temperature?

Up to 70–90 °C from oil-injected screws; enough for boiler feed or process washing.

Does it change compressor efficiency?

No, as long as cooling stays adequate when the heat is not needed.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.