Gas Turbine Output and Heat Rate at Site Ambient and Altitude

Gas turbine output and heat rate at site temperature and altitude from ISO ratings with user temperature coefficients, plus extra inlet pressure loss.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Illustrative 50 MW at 35 C and 500 mCold day at sea levelHigh-altitude aero-derivative

Accepted: 0.1 to 1,000 MW
Accepted: 5,400 to 21,600 kJ/kWh
Accepted: -33.15 to 56.85 °C
Accepted: 0 to 4,000 m
Accepted: 0 to 2 %
Accepted: 0 to 1 %
Accepted: 0 to 5,000 Pa
Accepted: 0 to 5 %

Results

Output scales with air mass flow, so with site pressure (ISA at the altitude) and roughly linearly with temperature (about 0.5–0.9 %/K for heavy-duty units, more for aero-derivatives); heat rate rises about 0.1–0.2 %/K. Altitude barely changes heat rate. Use the maker's correction curves where available; the coefficients here are the user's.

Site atmospheric pressure (ISA)77.541kPa
Pressure factor0.76527
Temperature factor on output0.91000
Site output27.410MW
Site heat rate9,384.0kJ/kWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 50 MW at 35 C and 500 m. The inputs, in the units selected above:

InputValue
ISO rated output50.000 MW
ISO heat rate (LHV)10,000 kJ/kWh
Site ambient temperature35.000 °C
Site altitude500.00 m
Output loss per kelvin above 15 °C0.70000 %
Heat rate rise per kelvin above 15 °C0.18000 %
Extra inlet pressure loss500.00 Pa
Output loss per 1 kPa inlet loss1.5000 %

Applying the formula below gives:

ResultValue
Site atmospheric pressure (ISA)95.461 kPa
Pressure factor0.94213
Temperature factor on output0.86000
Site output40.208 MW
Site heat rate10,360 kJ/kWh

Open this example in the calculator and change any input.

Formula

\(P = P_{ISO}\frac{p_a}{101.325}\left[1 - k_P(T_a - 15)\right]\left(1 - k_{in}\Delta p_{in}\right), \quad HR = HR_{ISO}\left[1 + k_{HR}(T_a - 15)\right]\)

Variables

Symbol Meaning SI unit
\(P_{ISO}\) ISO rated output W
\(HR_{ISO}\) ISO heat rate (LHV) J/J
\(T_a\) Site ambient temperature K
\(z\) Site altitude m
\(k_P\) Output loss per kelvin above 15 °C -
\(k_{HR}\) Heat rate rise per kelvin above 15 °C -
\(\Delta p_{in}\) Extra inlet pressure loss Pa
\(k_{in}\) Output loss per 1 kPa inlet loss -
\(p_a\) Site atmospheric pressure (ISA) Pa
\(f_p\) Pressure factor -
\(f_T\) Temperature factor on output -
\(P\) Site output W
\(HR\) Site heat rate J/J

Method and standards

Site correction.

Where it is used

  • Bidding site capacity.
  • Assessing inlet cooling and filter changes.

Common mistakes

  • Applying ISO output at a hot, high site.
  • Using gauge for absolute pressure.

Assumptions and limits

  • Linear corrections near ISO conditions.

References

  • Linear site correction with ISO 2533 pressure

Questions and answers

Why does a gas turbine lose output on hot days?

Hot air is less dense, so the fixed-volume compressor pushes less mass, and compressor work per kg rises.

Does altitude change efficiency?

Hardly: output falls with pressure but so does fuel flow, leaving heat rate nearly unchanged.

What do the defaults represent?

An illustrative 50 MW unit with a 10,000 kJ/kWh heat rate at 35 °C and 500 m with 0.7 %/K and 0.18 %/K coefficients and 0.5 kPa extra inlet loss.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Boyce, Gas Turbine Engineering Handbook, 4th ed. (Butterworth-Heinemann, 2012), Kehlhofer, Hannemann, Stirnimann and Rukes, Combined-Cycle Gas and Steam Turbine Power Plants, 3rd ed. (PennWell, 2009)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.