Rain-Type Condenser Size and Water Distribution

Section and diameter of a rain-type condenser from the vapour load (Hugot: 0.1–0.2 m² per t/h), the water pipe and the tray holes (3 × pipe area).

Sugar mill and cogenerationCondenser and cooling tower

Inputs

Examples: 11 t/h vapourLarge condenser

Square metres of section for each tonne per hour of vapour; Hugot 0.1–0.2.

Results

Hugot: holes of about 15 mm, at least 1.8 m (better 2.4 m) of fall above the vapour entry, and an approach of 2–5 °C; these are not checked here.

The injection water is an input and is not tied to the vapour load: check it with the condenser heat balance (multijet or barometric condenser water).

Condenser section1.6500m²
Condenser diameter1.4494m
Water pipe section0.076389m²
Water pipe diameter311.87mm
Total hole area (3 a_p)0.22917m²
Number of holes1,297.0

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 11 t/h vapour. The inputs, in the units selected above:

InputValue
Vapour to condense11.000 t/h
Section per t/h of vapour (m² per t/h)0.15000 m²
Injection water550.00 m³/h
Water velocity in the supply pipe2.0000 m/s
Hole diameter15.000 mm

Applying the formula below gives:

ResultValue
Condenser section1.6500 m²
Condenser diameter1.4494 m
Water pipe section0.076389 m²
Water pipe diameter311.87 mm
Total hole area (3 a_p)0.22917 m²
Number of holes1,297.0

Open this example in the calculator and change any input.

Formula

\(S = \sigma Q, \quad D = \sqrt{4S/\pi}, \quad a_p = \frac{Q_w}{V_w}, \quad a_h = 3a_p, \quad n = \frac{a_h}{\pi d_h^2/4}\)

Variables

Symbol Meaning SI unit
\(Q\) Vapour to condense kg/s
\(\sigma\) Section per t/h of vapour (m² per t/h) m²
\(Q_w\) Injection water m³/s
\(V_w\) Water velocity in the supply pipe m/s
\(d_h\) Hole diameter m
\(S\) Condenser section m²
\(D\) Condenser diameter m
\(a_p\) Water pipe section m²
\(d_p\) Water pipe diameter m
\(a_h\) Total hole area (3 a_p) m²
\(n\) Number of holes -

Method and standards

Hugot's proportions.

Where it is used

  • Designing rain condensers.
  • Retrofitting condensers.

Common mistakes

  • Too few holes: the tray overflows.
  • Too short a fall.

Assumptions and limits

  • Hugot's proportions from practice.
  • σ is in m² per t/h of vapour and is shown in m² in every unit system.
  • The injection water is not checked against the vapour load, and the fall height and approach are not computed.

References

  • Hugot
  • Handbook of Cane Sugar Engineering
  • 3rd ed. (Elsevier, 1986)
  • ch. 40
  • rain-type condensers
  • pp. 893–895

Questions and answers

How does a rain condenser work?

Water falls as rain from a perforated tray through the rising vapour; no nozzles are needed.

Why three times the pipe area for holes?

The holes discharge under little head; ample area keeps the tray from flooding.

Section per t/h?

Hugot: 0.1–0.2 m² per tonne of vapour per hour.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.