FireCADCalc

Water Pipe Sizing by Velocity (Feedwater, Condensate)

Inside diameter of a feedwater, condensate or cooling water pipe for a mass flow and design velocity, with water density from IAPWS-IF97.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserIAPWS-IF97 (water and steam)Pump

Inputs

Examples: Feedwater 51 t/h at 105 °C, 90 bar(a), 2.5 m/s, check DN80 (77.9 mm)Condensate 5 t/h at 90 °C, 3 bar(a), 1.5 m/sCooling water 500 t/h at 32 °C, 4 bar(a), 2 m/s, check DN300 (303.2 mm)

From your piping specification; the calculator does not suggest one.

Results

Inside diameter for the design velocity298.08mm
Velocity in the chosen pipe1.9330m/s
Volume flow502.43m³/h
Water density995.16kg/m³

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Feedwater 51 t/h at 105 °C, 90 bar(a), 2.5 m/s, check DN80 (77.9 mm). The inputs, in the units selected above:

InputValue
Water flow51,000 kg/h
Water pressure (absolute)90.000 bar
Water temperature105.00 °C
Design velocity2.5000 m/s
Chosen pipe inside diameter to check (0 = skip)77.900 mm

Applying the formula below gives:

ResultValue
Inside diameter for the design velocity86.744 mm
Velocity in the chosen pipe3.0998 m/s
Volume flow53.187 m³/h
Water density958.88 kg/m³

Open this example in the calculator and change any input.

Formula

\(Q = \frac{\dot m}{\rho} \qquad D = \sqrt{\frac{4\,Q}{\pi\,u}} \qquad u_{sel} = \frac{4\,Q}{\pi\,D_{sel}^2}\)

Variables

Symbol Meaning SI unit
\(\dot m\) water flow kg/s
\(p\) water pressure, absolute Pa
\(T\) water temperature K
\(u\) design velocity m/s
\(D_{sel}\) chosen pipe inside diameter m
\(D\) inside diameter for the design velocity m
\(u_{sel}\) velocity in the chosen pipe m/s
\(Q\) volume flow m³/s
\(\rho\) water density kg/m³

Method and standards

Continuity for a full circular pipe with the liquid density from FireCAD's IAPWS-IF97 implementation.

Where it is used

  • Sizing feedwater, cooling water and make-up water lines.
  • Pump suction and discharge line selection.
  • Checking existing lines after a flow increase.

Common mistakes

  • Using the same velocity for suction and discharge: suction needs lower velocity.
  • Ignoring hot-water density and viscosity.
  • Selecting by velocity alone on long lines.

Assumptions and limits

  • The water must be liquid below its saturation temperature at the pressure entered. Flashing condensate is two-phase and is not covered. At exactly saturation the IF97 phase test may treat the state as vapour and reject it: enter a pressure slightly above the saturation pressure for saturated condensate.

  • Liquid water only (the pressure must be above the saturation pressure).

  • Sizing by velocity; check the pressure drop and, for pump suction lines, NPSH.

References

  • IAPWS R7-97(2012) IF97 (density)
  • Continuity equation

Questions and answers

How do I size a feedwater pipe?

Volume flow = mass flow ÷ density; area = volume flow ÷ velocity. 51 t/h at 105 °C is 53.2 m³/h; at 2.5 m/s it needs an 87 mm bore. A DN80 pipe (77.9 mm) would run at 3.1 m/s.

Why enter the mass flow?

Boiler balances are in mass. Hot water is lighter (959 kg/m³ at 105 °C), so the same mass needs about 4 % more volume than cold water.

Does this cover condensate with flash steam?

No. Condensate lines after steam traps carry flash steam and need a two-phase method; this is for liquid lines.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.