FireCADCalc

Drum Level from DP Transmitter (Density Compensation)

True boiler drum level from a differential pressure transmitter with a cold reference leg, compensated for water and steam density at drum pressure (IAPWS-IF97).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperIAPWS-IF97 (water and steam)Boiler

Inputs

Examples: 66 bar(a), dP 3.2 kPa, taps 760 mm apart, reference leg 50 °C18 bar(a), dP 2.5 kPa, 600 mm, 40 °C150 bar(a), dP 4.0 kPa, 900 mm, 60 °C

Results

True water level above the lower tap395.93mm
Level, share of the tap distance65.988%
Level an uncompensated (cold-water) setting would show343.27mm
Uncompensated reading minus true level-52.662mm

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 66 bar(a), dP 3.2 kPa, taps 760 mm apart, reference leg 50 °C. The inputs, in the units selected above:

InputValue
Drum pressure (absolute)66.000 bar
Measured differential pressure (reference leg minus drum leg)3.2000 kPa
Vertical distance between the taps760.00 mm
Reference (cold) leg temperature50.000 °C

Applying the formula below gives:

ResultValue
True water level above the lower tap562.27 mm
Level, share of the tap distance73.983 %
Level an uncompensated (cold-water) setting would show430.68 mm
Uncompensated reading minus true level-131.59 mm

Open this example in the calculator and change any input.

Formula

\(\Delta p = \rho_r g H - \rho_w g h - \rho_s g (H - h) \;\Rightarrow\; h = \frac{(\rho_r - \rho_s) g H - \Delta p}{g(\rho_w - \rho_s)} \qquad h_u = \frac{\rho_r g H - \Delta p}{\rho_r g}\)

Variables

Symbol Meaning SI unit
\(p\) drum pressure Pa
\(\Delta p\) measured differential pressure Pa
\(H\) tap distance m
\(T_r\) reference leg temperature K
\(h\) true level above lower tap m
\(h/H\) level share –
\(h_u\) uncompensated level m
\(\varepsilon\) uncompensated minus true m
\(\rho_r\) reference leg density (IF97) kg/m³
\(\rho_w\) saturated water density (IF97) kg/m³
\(\rho_s\) saturated steam density (IF97) kg/m³
\(g\) standard gravity m/s²

Method and standards

Hydrostatic balance with densities from FireCAD's IAPWS-IF97; the transmitter's high side on the reference leg.

Where it is used

  • Configuring drum level transmitters and DCS compensation.
  • Explaining level errors at start-up.
  • Cross-checking against gauge glasses.

Common mistakes

  • Forgetting the steam above the water in the variable leg.
  • Assuming the reference leg is at drum temperature.
  • Mixing up high and low sides.

Assumptions and limits

  • Reference leg full and at one temperature; equilibrium drum.

References

  • Hydrostatic balance of drum and reference legs
  • IAPWS R7-97 IF97

Questions and answers

Why does drum level need compensation?

Hot drum water is much lighter than the cold reference leg. At 66 bar(a) with taps 760 mm apart and a 3.2 kPa reading, the true level is 562 mm, but a setting for cold water would show 431 mm.

Which densities change?

Saturated water and steam in the drum change with pressure; the reference leg depends on its temperature.

Is compensation needed on low-pressure boilers?

The error is smaller but still several per cent at 10–20 bar; compensation also keeps level correct during start-up.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.