Worked example
Example: 66 bar(a), dP 3.2 kPa, taps 760 mm apart, reference leg 50 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Drum pressure (absolute) | 66.000 bar |
| Measured differential pressure (reference leg minus drum leg) | 3.2000 kPa |
| Vertical distance between the taps | 760.00 mm |
| Reference (cold) leg temperature | 50.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| True water level above the lower tap | 562.27 mm |
| Level, share of the tap distance | 73.983 % |
| Level an uncompensated (cold-water) setting would show | 430.68 mm |
| Uncompensated reading minus true level | -131.59 mm |
Open this example in the calculator and change any input.
Formula
\(\Delta p = \rho_r g H - \rho_w g h - \rho_s g (H - h) \;\Rightarrow\; h = \frac{(\rho_r - \rho_s) g H - \Delta p}{g(\rho_w - \rho_s)} \qquad h_u = \frac{\rho_r g H - \Delta p}{\rho_r g}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p\) | drum pressure | Pa |
| \(\Delta p\) | measured differential pressure | Pa |
| \(H\) | tap distance | m |
| \(T_r\) | reference leg temperature | K |
| \(h\) | true level above lower tap | m |
| \(h/H\) | level share | – |
| \(h_u\) | uncompensated level | m |
| \(\varepsilon\) | uncompensated minus true | m |
| \(\rho_r\) | reference leg density (IF97) | kg/m³ |
| \(\rho_w\) | saturated water density (IF97) | kg/m³ |
| \(\rho_s\) | saturated steam density (IF97) | kg/m³ |
| \(g\) | standard gravity | m/s² |
Method and standards
Hydrostatic balance with densities from FireCAD's IAPWS-IF97; the transmitter's high side on the reference leg.
Where it is used
- Configuring drum level transmitters and DCS compensation.
- Explaining level errors at start-up.
- Cross-checking against gauge glasses.
Common mistakes
- Forgetting the steam above the water in the variable leg.
- Assuming the reference leg is at drum temperature.
- Mixing up high and low sides.
Assumptions and limits
- Reference leg full and at one temperature; equilibrium drum.
References
- Hydrostatic balance of drum and reference legs
- IAPWS R7-97 IF97
Questions and answers
Why does drum level need compensation?
Hot drum water is much lighter than the cold reference leg. At 66 bar(a) with taps 760 mm apart and a 3.2 kPa reading, the true level is 562 mm, but a setting for cold water would show 431 mm.
Which densities change?
Saturated water and steam in the drum change with pressure; the reference leg depends on its temperature.
Is compensation needed on low-pressure boilers?
The error is smaller but still several per cent at 10–20 bar; compensation also keeps level correct during start-up.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.