Pneumatic Actuator Stroke Time

Time to fill or vent a pneumatic actuator over its stroke from actuator swept volume, pressures and the air flow the positioner, booster or solenoid can deliver.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 12 L actuator to 3 bar(a), 6 m³/hVenting 40 L from 5 bar(a), 30 m³/h

Results

Isothermal filling at constant average delivery; real flow falls as the actuator pressure approaches supply, so add 20–50 %. Volume boosters or quick-exhaust valves shorten trip times.

Free air needed157.38L
Stroke time18.886s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 12 L actuator to 3 bar(a), 6 m³/h. The inputs, in the units selected above:

InputValue
Actuator swept volume plus dead volume12.000 L
Starting pressure (absolute)1.0132 bar
End pressure (absolute)3.0000 bar
Air delivery (free air, at 1.01325 bar)6.0000 m³/h

Applying the formula below gives:

ResultValue
Free air needed23.529 L
Stroke time14.118 s

Open this example in the calculator and change any input.

Formula

\(V_n = V\frac{|p_2 - p_1|}{p_0}, \quad t = \frac{V_n}{\dot V_n}\)

Variables

Symbol Meaning SI unit
\(V\) Actuator swept volume plus dead volume m³
\(p_1\) Starting pressure (absolute) Pa
\(p_2\) End pressure (absolute) Pa
\(\dot V_n\) Air delivery (free air, at 1.01325 bar) m³/s
\(V_{n}\) Free air needed m³
\(t\) Stroke time s

Method and standards

Isothermal fill.

Where it is used

  • Shut-down valve stroke checks.
  • Booster selection.

Common mistakes

  • Ignoring tubing volume.
  • Using supply pressure instead of the actuator range.

Assumptions and limits

  • Isothermal fill at constant volume and constant average air delivery. Real filling is closer to adiabatic and the delivery falls as the actuator pressure approaches the supply, so real stroke times are longer; the 20–50 % allowance in the note is a rule of thumb, not a sourced figure. Time it on the valve where it matters (ESD valves).

  • Isothermal; average delivery.

References

  • Isothermal mass balance of the actuator volume (definitions)

Questions and answers

Why are large actuators slow?

Their volume must be filled with air through small positioner ports; delivery, not the spring, usually limits speed.

What is a typical requirement?

Emergency shut-down valves often need closure in 2–10 s; control valves 5–30 s full stroke.

What do the defaults represent?

A 12 L actuator stroked from atmospheric to 3 bar(a) with 6 m³/h of free air.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.