Control Valve Cavitation Index (σ)

Cavitation index σ of a control valve for liquid from inlet, outlet and vapour pressures, against the valve's incipient and constant cavitation values.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 8 / 3 bar(a), vapour 0.2 bar, σi 2Boiler feed: 60 / 10 bar(a), hot water pv 4.8 bar, σi 1.5Gentle drop 5 / 4 bar(a), cold water

From the valve maker for the valve type and opening.

Results

σ at or below the incipient value: cavitation is expected; consider anti-cavitation trim or staging.

Cavitation index (p₁ − p_v)/(p₁ − p₂)1.5600
Pressure drop ratio (p₁ − p₂)/(p₁ − p_v)64.103%
Largest drop before incipient cavitation390.00kPa

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 8 / 3 bar(a), vapour 0.2 bar, σi 2. The inputs, in the units selected above:

InputValue
Inlet pressure (absolute)8.0000 bar
Outlet pressure (absolute)3.0000 bar
Vapour pressure of the liquid0.20000 bar
Incipient cavitation index of the valve2.0000 -

Applying the formula below gives:

ResultValue
Cavitation index (p₁ − p_v)/(p₁ − p₂)1.5600
Pressure drop ratio (p₁ − p₂)/(p₁ − p_v)64.103 %
Largest drop before incipient cavitation390.00 kPa

Open this example in the calculator and change any input.

Formula

\(\sigma = \frac{p_1 - p_v}{p_1 - p_2}, \quad \Delta p_i = \frac{p_1 - p_v}{\sigma_i}\)

Variables

Symbol Meaning SI unit
\(p_1\) Inlet pressure (absolute) Pa
\(p_2\) Outlet pressure (absolute) Pa
\(p_v\) Vapour pressure of the liquid Pa
\(\sigma_i\) Incipient cavitation index of the valve -
\(\sigma\) Cavitation index (p₁ − p_v)/(p₁ − p₂) -
\(x_F\) Pressure drop ratio (p₁ − p₂)/(p₁ − p_v) -
\(\Delta p_i\) Largest drop before incipient cavitation Pa

Method and standards

Definition of the cavitation index.

Where it is used

  • Control valve selection.
  • Diagnosing noisy valves.

Common mistakes

  • Using gauge pressures with vapour pressure.
  • Ignoring the valve's own σ values.

Assumptions and limits

  • σ_i from the maker usually comes from tests on a small valve at modest pressure. ISA-RP75.23 corrects it for valve size and upstream pressure (scale effects), which generally make larger valves cavitate at a higher σ; those corrections are not applied, so the result may be optimistic for large valves or high pressures.

  • Liquid service.

References

  • Cavitation index σ = (p₁ − p_v)/(p₁ − p₂) (ISA-RP75.23 definition)

Questions and answers

8 bar(a) in, 3 bar(a) out, vapour 0.2 bar?

σ = 1.56: below 2, so cavitation is likely.

What drop is safe?

390 kPa for σ_i = 2.

What is the difference from flashing?

In flashing the outlet stays below the vapour pressure; bubbles do not collapse.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.