Worked example
Example: Kv 100 at 1 bar, water. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Coefficient known | Kv |
| Value of the known coefficient | 100.00 - |
| Pressure drop across the valve | 1.0000 bar |
| Specific gravity of the liquid (water = 1) | 1.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Kv | 100.00 |
| Cv | 115.61 |
| Liquid flow at the pressure drop | 100.00 m³/h |
Open this example in the calculator and change any input.
Formula
\(K_v = 0.865\, C_v\)
\(Q = K_v \sqrt{\frac{\Delta p / 1\,\text{bar}}{SG}} \ \text{m}^3/\text{h}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{known}\) | which coefficient is known | - |
| \(K\) | value of the known coefficient | - |
| \(\Delta p\) | pressure drop | Pa |
| \(SG\) | specific gravity | - |
| \(K_v\) | Kv: m³/h at 1 bar drop | - |
| \(C_v\) | Cv: US gpm at 1 psi drop | - |
| \(Q\) | liquid flow | m³/s |
Method and standards
Kv is the flow of water in m³/h at a 1 bar drop; Cv is US gallons per minute at a 1 psi drop. The ratio follows from the exact unit definitions: Kv = Cv × 0.2271 m³/h per gpm × √(14.504 psi per bar) = 0.865 Cv (flow rises with the square root of the pressure drop, from 1 psi to 1 bar).
Where it is used
- Comparing valves from European and American makers.
- Checking flow through a manual or control valve.
- Converting data-sheet coefficients.
Common mistakes
- Using Kv where the formula expects Cv.
- Forgetting the square root on pressure drop.
- Applying liquid formulas to gas or steam.
Assumptions and limits
- Turbulent, non-choked liquid flow.
References
- Definitions of Kv and Cv
Questions and answers
How do I convert Kv to Cv?
Cv = 1.156 Kv, and Kv = 0.865 Cv. A Kv 100 valve is Cv 115.6.
How much water passes a Kv 100 valve at 1 bar?
100 m³/h by definition; at 4 bar twice as much, since flow rises with the square root of the drop.
Is this enough to size a control valve?
For clean liquids without choking, as a check; use the IEC 60534 calculators for flashing, cavitating or gas service.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.