IDMT Overcurrent Relay Operating Time

Operating time of an IDMT overcurrent relay from fault current, CT ratio, pickup and time multiplier for standard, very and extremely inverse curves.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 400/1, 1 A, TMS 0.2, SI, 4 kAVery inverse 200/1, 1.25 A, TMS 0.3, 3 kAExtremely inverse 10× setting

Results

Standard IEC-type inverse-time equation t = TMS·k/(PSM^α − 1); curves are commonly considered valid up to about 20 times setting. Grade upstream relays 0.3–0.4 s above downstream ones.

Plug setting multiplier I_f/(CT·I_s)10.000
Operating time0.080808s
Time at TMS = 10.80808s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 400/1, 1 A, TMS 0.2, SI, 4 kA. The inputs, in the units selected above:

InputValue
Fault current (primary)4,000.0 A
CT ratio (primary amps per secondary amp)400.00 -
Relay pickup setting (secondary amps)1.0000 A
Time multiplier setting0.20000 -
CurveStandard inverse (0.14, 0.02)

Applying the formula below gives:

ResultValue
Plug setting multiplier I_f/(CT·I_s)10.000
Operating time0.59412 s
Time at TMS = 12.9706 s

Open this example in the calculator and change any input.

Formula

\(PSM = \frac{I_f}{CT\cdot I_s}, \quad t = TMS\frac{k}{PSM^\alpha - 1}\)

Variables

Symbol Meaning SI unit
\(I_f\) Fault current (primary) A
\(CT\) CT ratio (primary amps per secondary amp) -
\(I_s\) Relay pickup setting (secondary amps) A
\(TMS\) Time multiplier setting -
\(\text{curve}\) Curve -
\(PSM\) Plug setting multiplier I_f/(CT·I_s) -
\(t\) Operating time s
\(t_{TMS=1}\) Time at TMS = 1 s

Method and standards

Inverse-time equation.

Where it is used

  • Feeder and transformer protection grading.
  • Checking relay settings.

Common mistakes

  • Mixing primary and secondary currents.
  • Using the curve beyond 20× setting.

Assumptions and limits

  • Standard IEC-type curves. A PSM above about 20 is flagged (most relays go definite-time there).
  • The curve constants are the widely published IEC values (standard inverse 0.14/0.02, very inverse 13.5/1, extremely inverse 80/2, long-time inverse 120/1).

References

  • Inverse-time overcurrent characteristic t = TMS·k/((I/I_s)^α − 1) with the standard inverse
  • very inverse
  • extremely inverse and long-time constants (IEC 60255-151 form)

Questions and answers

What is plug setting multiplier?

Fault current as a multiple of the relay's pickup current, both referred to the same side of the CT.

How are relays graded?

Each upstream relay operates 0.3–0.4 s later than the one below it at the maximum fault current both see.

What do the defaults represent?

A 400/1 CT, 1 A setting, TMS 0.2, standard inverse, 4 kA fault.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.