FireCADCalc

Total Harmonic Distortion (THD) and TDD of Current

Total harmonic distortion, total demand distortion, total rms current and distortion power factor from the fundamental and the harmonic currents of a load.

Thermal power plantProcess steam and utilitiesElectric motor

Inputs

Examples: Mixed load 100 A fundamentalSix-pulse driveLED and SMPS lighting

Harmonic currents (rms)

Results

The same sums give voltage THD when voltages are entered. Limits at the point of common coupling come from IEEE 519 or your utility, not from this page.

Harmonic current, rms of all harmonics22.383A
Total harmonic distortion (on the fundamental)22.383%
Total demand distortion (on the maximum demand current)18.653%
Total rms current102.47A
Distortion power factor 1/√(1 + THD²)97.585%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Mixed load 100 A fundamental. The inputs, in the units selected above:

InputValue
Fundamental current (50 or 60 Hz)100.00 A
3rd harmonic5.0000 A
5th harmonic18.000 A
7th harmonic10.000 A
11th harmonic6.0000 A
13th harmonic4.0000 A
All other harmonics together (rms)0 A
Maximum demand load current (for TDD)120.00 A

Applying the formula below gives:

ResultValue
Harmonic current, rms of all harmonics22.383 A
Total harmonic distortion (on the fundamental)22.383 %
Total demand distortion (on the maximum demand current)18.653 %
Total rms current102.47 A
Distortion power factor 1/√(1 + THD²)97.585 %

Open this example in the calculator and change any input.

Formula

\(I_H = \sqrt{\sum_h I_h^2}, \quad THD_I = \frac{I_H}{I_1}, \quad TDD = \frac{I_H}{I_L}\)

\(I_{rms} = \sqrt{I_1^2 + I_H^2}, \quad \cos\varphi_d = \frac{1}{\sqrt{1 + THD^2}}\)

Variables

Symbol Meaning SI unit
\(I_1\) Fundamental current (50 or 60 Hz) A
\(I_3\) 3rd harmonic A
\(I_5\) 5th harmonic A
\(I_7\) 7th harmonic A
\(I_{11}\) 11th harmonic A
\(I_{13}\) 13th harmonic A
\(I_o\) All other harmonics together (rms) A
\(I_L\) Maximum demand load current (for TDD) A
\(I_H\) Harmonic current, rms of all harmonics A
\(THD_I\) Total harmonic distortion (on the fundamental) -
\(TDD\) Total demand distortion (on the maximum demand current) -
\(I_{rms}\) Total rms current A
\(\cos\varphi_d\) Distortion power factor 1/√(1 + THD²) -

Method and standards

The harmonic currents are combined as a root-sum-square and related to the fundamental (THD) or to the maximum demand load current (TDD), as defined in IEEE 519. The distortion power factor shows how much the harmonics lower the true power factor.

Where it is used

  • Checking drives, UPS and LED lighting against utility limits.
  • Sizing harmonic filters and neutral conductors.
  • Explaining low true power factor with good displacement power factor.

Common mistakes

  • Comparing THD at light load with TDD limits.
  • Adding harmonic currents directly instead of as squares.
  • Forgetting triplen (3rd, 9th) currents add in the neutral.

Assumptions and limits

  • Steady-state rms values.
  • Limits are for the point of common coupling in your utility's rules.

References

  • IEEE 519 definitions of THD and TDD
  • IEC 61000-2-2 harmonic definitions

Questions and answers

What THD does a six-pulse drive cause?

With 35 % fifth, 22 % seventh and smaller higher harmonics, about 43 % THD; the rms current is 8.7 % above the fundamental.

What is the difference between THD and TDD?

THD divides the harmonics by the fundamental at the moment; TDD divides by the maximum demand current, so light loads do not look worse than they matter. IEEE 519 limits are in TDD.

Why does harmonic current matter?

It heats cables, transformers and capacitors without doing work, and it distorts the voltage for other users.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.