Worked example
Example: Mixed load 100 A fundamental. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fundamental current (50 or 60 Hz) | 100.00 A |
| 3rd harmonic | 5.0000 A |
| 5th harmonic | 18.000 A |
| 7th harmonic | 10.000 A |
| 11th harmonic | 6.0000 A |
| 13th harmonic | 4.0000 A |
| All other harmonics together (rms) | 0 A |
| Maximum demand load current (for TDD) | 120.00 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| Harmonic current, rms of all harmonics | 22.383 A |
| Total harmonic distortion (on the fundamental) | 22.383 % |
| Total demand distortion (on the maximum demand current) | 18.653 % |
| Total rms current | 102.47 A |
| Distortion power factor 1/√(1 + THD²) | 97.585 % |
Open this example in the calculator and change any input.
Formula
\(I_H = \sqrt{\sum_h I_h^2}, \quad THD_I = \frac{I_H}{I_1}, \quad TDD = \frac{I_H}{I_L}\)
\(I_{rms} = \sqrt{I_1^2 + I_H^2}, \quad \cos\varphi_d = \frac{1}{\sqrt{1 + THD^2}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_1\) | Fundamental current (50 or 60 Hz) | A |
| \(I_3\) | 3rd harmonic | A |
| \(I_5\) | 5th harmonic | A |
| \(I_7\) | 7th harmonic | A |
| \(I_{11}\) | 11th harmonic | A |
| \(I_{13}\) | 13th harmonic | A |
| \(I_o\) | All other harmonics together (rms) | A |
| \(I_L\) | Maximum demand load current (for TDD) | A |
| \(I_H\) | Harmonic current, rms of all harmonics | A |
| \(THD_I\) | Total harmonic distortion (on the fundamental) | - |
| \(TDD\) | Total demand distortion (on the maximum demand current) | - |
| \(I_{rms}\) | Total rms current | A |
| \(\cos\varphi_d\) | Distortion power factor 1/√(1 + THD²) | - |
Method and standards
The harmonic currents are combined as a root-sum-square and related to the fundamental (THD) or to the maximum demand load current (TDD), as defined in IEEE 519. The distortion power factor shows how much the harmonics lower the true power factor.
Where it is used
- Checking drives, UPS and LED lighting against utility limits.
- Sizing harmonic filters and neutral conductors.
- Explaining low true power factor with good displacement power factor.
Common mistakes
- Comparing THD at light load with TDD limits.
- Adding harmonic currents directly instead of as squares.
- Forgetting triplen (3rd, 9th) currents add in the neutral.
Assumptions and limits
- Steady-state rms values.
- Limits are for the point of common coupling in your utility's rules.
References
- IEEE 519 definitions of THD and TDD
- IEC 61000-2-2 harmonic definitions
Questions and answers
What THD does a six-pulse drive cause?
With 35 % fifth, 22 % seventh and smaller higher harmonics, about 43 % THD; the rms current is 8.7 % above the fundamental.
What is the difference between THD and TDD?
THD divides the harmonics by the fundamental at the moment; TDD divides by the maximum demand current, so light loads do not look worse than they matter. IEEE 519 limits are in TDD.
Why does harmonic current matter?
It heats cables, transformers and capacitors without doing work, and it distorts the voltage for other users.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.