Lighting Maintenance Factor and Initial Illuminance

Maintenance factor from lumen depreciation, survival, luminaire and room surface factors, and the initial illuminance needed to keep a maintained value.

Food, dairy and textile

Inputs

Examples: Illustrative LED officeDirty factoryClean room long life

Accepted: 1,000 to 2,777,800 h
Accepted: 0 to 2,777,800 h
Accepted: 50 to 100 %
Accepted: 40 to 100 %
Accepted: 50 to 100 %
Accepted: 1 to 100,000 lx

Results

MF = LLMF × LSF × LMF × RSMF, with LLMF assumed to fall exponentially to 0.7 at L₇₀. Use the maker's LLMF table where given; constant-light-output drivers can recover much of the over-lighting energy.

Lamp lumen maintenance factor93.115%
Maintenance factor86.690%
Initial illuminance to design for865.15lx
Over-lighting when new15.353%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative LED office. The inputs, in the units selected above:

InputValue
Rated life to 70 % lumens50,000 h
Operating hours to maintenance25,000 h
Lamp survival factor100.00 %
Luminaire maintenance factor90.000 %
Room surface maintenance factor95.000 %
Maintained illuminance required500.00 lx

Applying the formula below gives:

ResultValue
Lamp lumen maintenance factor83.666 %
Maintenance factor71.534 %
Initial illuminance to design for698.96 lx
Over-lighting when new39.793 %

Open this example in the calculator and change any input.

Formula

\(MF = LLMF\cdot LSF\cdot LMF\cdot RSMF, \quad LLMF = 0.7^{t/L_{70}}, \quad E_i = \frac{E_m}{MF}\)

Variables

Symbol Meaning SI unit
\(L_{70}\) Rated life to 70 % lumens s
\(t\) Operating hours to maintenance s
\(LSF\) Lamp survival factor -
\(LMF\) Luminaire maintenance factor -
\(RSMF\) Room surface maintenance factor -
\(E_m\) Maintained illuminance required lx
\(LLMF\) Lamp lumen maintenance factor -
\(MF\) Maintenance factor -
\(E_i\) Initial illuminance to design for lx
\(1/MF - 1\) Over-lighting when new -

Method and standards

Maintenance factor.

Where it is used

  • Lighting design by the lumen method.
  • Maintenance planning.

Common mistakes

  • Using MF = 1 for LED.
  • Ignoring room surface dirt in industry.

Assumptions and limits

  • Exponential lumen depreciation.

References

  • Maintenance factor components
  • Lighting Handbook practice (lumen method, maintenance factor components)

Questions and answers

What maintenance factor is typical?

About 0.7–0.85 for clean offices with LED; 0.5–0.65 in dirty industrial areas.

Why design for initial illuminance above the target?

Lamps dim and fittings get dirty; the installation must still give the maintained value at the end of the maintenance period.

What do the defaults represent?

An illustrative LED installation with L70 of 50,000 h, maintenance at 25,000 h, LMF 0.9, RSMF 0.95, for 500 lx maintained.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.