FireCADCalc

Emergency Lighting Battery Capacity

Battery capacity for a central emergency lighting system from luminaire load, duration, battery voltage, inverter efficiency and ageing and temperature factors.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 40 x 8 W for 3 h at 216 V1 h, 100 x 5 W at 110 VSmall 24 V system 12 x 3 W, 3 h

Accepted: 1 to 10,000
Accepted: 0.0005 to 0.5 kW
Accepted: 0.5 to 24 h
Accepted: 6 to 1,000 V
Accepted: 50 to 100 %
Accepted: 1 to 2
Accepted: 1 to 2
Accepted: 30 to 100 %

Results

C = I·t·k_a·k_t/DoD with I = P/(ηV). Battery capacity also depends on the discharge rate (check the maker's table for the duration, often 1 or 3 hours); national rules set durations and test routines.

Total emergency load0.036000kW
Energy for the duration0.10800kWh
Battery discharge current1.6667A
Required battery capacity9.8214Ah

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 40 x 8 W for 3 h at 216 V. The inputs, in the units selected above:

InputValue
Number of luminaires40.000 -
Power per luminaire in emergency mode0.008000 kW
Rated duration3.0000 h
Battery voltage216.00 V
Inverter and wiring efficiency85.000 %
Ageing factor (end-of-life capacity margin)1.2500 -
Temperature factor1.1000 -
Allowed depth of discharge80.000 %

Applying the formula below gives:

ResultValue
Total emergency load0.32000 kW
Energy for the duration0.96000 kWh
Battery discharge current1.7429 A
Required battery capacity8.9869 Ah

Open this example in the calculator and change any input.

Formula

\(I = \frac{nP_l}{\eta V}, \quad C = \frac{Itk_ak_t}{DoD}\)

Variables

Symbol Meaning SI unit
\(n\) Number of luminaires -
\(P_l\) Power per luminaire in emergency mode W
\(t\) Rated duration s
\(V\) Battery voltage V
\(\eta\) Inverter and wiring efficiency -
\(k_a\) Ageing factor (end-of-life capacity margin) -
\(k_t\) Temperature factor -
\(DoD\) Allowed depth of discharge -
\(P\) Total emergency load W
\(E\) Energy for the duration J
\(I\) Battery discharge current A
\(C\) Required battery capacity C

Method and standards

Emergency battery sizing.

Where it is used

  • Central battery and inverter systems.
  • Checking existing installations.

Common mistakes

  • Ignoring the rate dependence of capacity.
  • Forgetting inverter losses.

Assumptions and limits

  • Constant power load.

References

  • Battery sizing for a constant-power load

Questions and answers

Why add ageing and temperature factors?

Batteries lose capacity with age and cold; sizing for end of life ensures the full duration is still met before replacement.

How long must emergency lighting run?

Often 1 or 3 hours depending on the building and national rules.

What do the defaults represent?

An illustrative 40 luminaires of 8 W for 3 hours from a 216 V battery, 85 % inverter efficiency, ageing 1.25, temperature 1.1 and 80 % depth of discharge.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.