Poultry House Ventilation Rate and Tunnel Air Speed

Minimum and maximum ventilation of a poultry house from bird numbers, live weight and rates per kg, fan count and the tunnel air speed over the birds.

Inputs

Examples: Illustrative 10000 broilersLayer houseYoung chicks

Accepted: 1 to 1,000,000
Accepted: 0.04 to 10 kg
Accepted: 0.1 to 5
Accepted: 1 to 20
Accepted: 360 to 108,000 m³/h
Accepted: 1 to 1,000 m²

Results

Ventilation is planned per kg of live weight: a small minimum rate in cold weather removes moisture, ammonia and CO₂, and a large hot-weather rate removes heat. In tunnel-ventilated houses the air speed over the birds (often 2–3 m/s for grown broilers) gives wind-chill cooling. Use the rates recommended for the breed, age and climate; fan capacity must be taken at the house's working static pressure.

Minimum ventilation5,250.0m³/h
Maximum ventilation30,000m³/h
Fans for maximum ventilation2.0000
Tunnel air speed at maximum0.26709m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 10000 broilers. The inputs, in the units selected above:

InputValue
Number of birds10,000 -
Live weight per bird2.0000 kg
Minimum ventilation per kg (m³/h per kg)0.70000 -
Hot-weather ventilation per kg (m³/h per kg)6.0000 -
Capacity of one fan at working pressure35,000 m³/h
House cross-section (width × average height)33.600 m²

Applying the formula below gives:

ResultValue
Minimum ventilation14,000 m³/h
Maximum ventilation120,000 m³/h
Fans for maximum ventilation4.0000
Tunnel air speed at maximum0.99206 m/s

Open this example in the calculator and change any input.

Formula

\(\dot V = n\,w\,r, \quad n_f = \left\lceil\frac{\dot V_{max}}{\dot V_f}\right\rceil, \quad v = \frac{\dot V_{max}}{A_x}\)

Variables

Symbol Meaning SI unit
\(n\) Number of birds -
\(w\) Live weight per bird kg
\(r_{min}\) Minimum ventilation per kg (m³/h per kg) -
\(r_{max}\) Hot-weather ventilation per kg (m³/h per kg) -
\(\dot V_f\) Capacity of one fan at working pressure m³/s
\(A_x\) House cross-section (width × average height) m²
\(\dot V_{min}\) Minimum ventilation m³/s
\(\dot V_{max}\) Maximum ventilation m³/s
\(n_f\) Fans for maximum ventilation -
\(v\) Tunnel air speed at maximum m/s

Method and standards

Poultry ventilation.

Where it is used

  • Broiler and layer house design.
  • Fan retrofits.

Common mistakes

  • Using fan capacity at zero static pressure.
  • Ignoring minimum ventilation in winter.

Assumptions and limits

  • Rates per kg as entered.

References

  • Ventilation per kg of live weight and tunnel air speed

Questions and answers

How many fans does a 10,000-bird broiler house need?

At 2 kg and 6 m³/h per kg, 120,000 m³/h: four 35,000 m³/h fans.

What tunnel air speed is used?

About 2–3 m/s for grown broilers; less for young birds.

What do the defaults represent?

An illustrative 10,000 broilers at 2 kg, 0.7 and 6 m³/h per kg, 35,000 m³/h fans, house 12 m wide and 2.8 m average height.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.