Worked example
Example: Illustrative 1000 m2 greenhouse. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Floor area | 1,000.0 m² |
| Heat gain per floor area (solar and other) | 0.40000 kW/m² |
| Outside dry-bulb temperature | 38.000 °C |
| Outside wet-bulb temperature | 24.000 °C |
| Pad saturation efficiency | 80.000 % |
| Allowed temperature rise from pad to fans | 4.0000 K |
| Pad face velocity | 1.2500 m/s |
| Capacity of one fan | 35,000 m³/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Air temperature leaving the pad | 26.800 °C |
| Air temperature at the fans | 30.800 °C |
| Air flow needed | 304,085 m³/h |
| Pad area | 67.574 m² |
| Fans needed | 9.0000 |
Open this example in the calculator and change any input.
Formula
\(T_p = T_{db} - \varepsilon(T_{db} - T_{wb}), \quad \dot V = \frac{q_s A_f}{\rho c_p \Delta T}, \quad A_p = \frac{\dot V}{v_p}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A_f\) | Floor area | m² |
| \(q_s\) | Heat gain per floor area (solar and other) | W/m² |
| \(T_{db}\) | Outside dry-bulb temperature | K |
| \(T_{wb}\) | Outside wet-bulb temperature | K |
| \(\varepsilon\) | Pad saturation efficiency | - |
| \(\Delta T\) | Allowed temperature rise from pad to fans | K |
| \(v_p\) | Pad face velocity | m/s |
| \(\dot V_f\) | Capacity of one fan | m³/s |
| \(T_p\) | Air temperature leaving the pad | K |
| \(T_x\) | Air temperature at the fans | K |
| \(\dot V\) | Air flow needed | m³/s |
| \(A_p\) | Pad area | m² |
| \(n\) | Fans needed | - |
Method and standards
Pad cooling.
Where it is used
- Greenhouses, polyhouses and poultry houses.
- Retrofitting cooling to existing houses.
Common mistakes
- Designing for the dry-bulb temperature alone.
- Pad velocity too high (water carry-over).
Assumptions and limits
- Uniform pad wetting; steady conditions.
References
- Greenhouse heat balance: cover conduction and air leakage
Questions and answers
How much pad does a 1,000 m² greenhouse need?
With 400 W/m² of heat gain and a 4 K rise, about 70 m² of 100 mm pad.
Why does it work poorly in humid weather?
The air can only cool to near its wet-bulb temperature, which is close to the dry bulb when humid.
What do the defaults represent?
An illustrative 1,000 m² greenhouse with 400 W/m² heat gain, outside 38 °C dry bulb and 24 °C wet bulb, 80 % pad, 4 K rise, 35,000 m³/h fans.