Worked example
Example: 10 m3 exothermic. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Reaction rate, mol of key reactant per m³ per second | 0.050000 - |
| Reacting volume | 10.000 m³ |
| Heat of reaction (negative: exothermic) | -120.00 kJ/mol |
| Agitator power to the liquid | 7.5000 kW |
| Cooling water in | 32.000 °C |
| Cooling water out | 40.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat to remove | 67.500 kW |
| Cooling water flow | 7.2696 t/h |
Open this example in the calculator and change any input.
Formula
\(\dot Q = r V(-\Delta H_r) + P_a, \quad \dot m = \frac{\dot Q}{h(t_2) - h(t_1)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(r\) | Reaction rate, mol of key reactant per m³ per second | - |
| \(V\) | Reacting volume | m³ |
| \(\Delta H_r\) | Heat of reaction (negative: exothermic) | J/mol |
| \(P_a\) | Agitator power to the liquid | W |
| \(t_1\) | Cooling water in | K |
| \(t_2\) | Cooling water out | K |
| \(\dot Q\) | Heat to remove | W |
| \(\dot m\) | Cooling water flow | kg/s |
Method and standards
Energy balance.
Where it is used
- Reactor and fermenter cooling.
- Cooling tower and pump sizing.
Common mistakes
- Average instead of peak rate.
- Forgetting agitator heat.
Assumptions and limits
- Steady state.
- The rate r is a plain number in mol of key reactant per m³ per second, and ΔH_r must be per mol of the same key reactant.
References
- Heat generation r V (−ΔH_r) plus agitator power; water enthalpies from IAPWS-IF97
Questions and answers
0.05 mol/(m³·s) in 10 m³ at −120 kJ/mol plus 7.5 kW of agitation?
67.5 kW: about 7.3 t/h of water for an 8 K rise.
Why add agitator power?
It all ends up as heat in the liquid.
Batch reactors?
The rate peaks early; size for the peak.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.