FireCADCalc

Thermic Fluid Heater Efficiency (Direct Method)

Efficiency of a thermic fluid (hot oil) heater from the fluid flow, specific heat and temperature rise, and the fuel flow and gross calorific value.

Refinery and petrochemicalChemical and fertiliserThermic fluid heatingFood, dairy and textileThermic fluid heater

Inputs

Examples: Coal-fired 2 MW: 25.6 kg/s, 260 to 290 °C, coal 520 kg/h at 18.6 MJ/kgOil-fired 1 MW: 13 kg/s, 230 to 260 °C, oil 100 kg/h at 43 MJ/kgWood-fired 3 MW: 45 kg/s, 270 to 295 °C, 1500 kg/h at 13 MJ/kgTherminol 55, coal-fired: 25 kg/s, 260 to 290 °C, 520 kg/h at 18.6 MJ/kg

Per kg of fuel as fired. For gas, convert the volumetric GCV and the gas flow to a mass basis first.

Fluid properties (used when the fluid is "enter the properties")

Results

Therminol 55 properties at 275 °C from Eastman Therminol 55 bulletin TF8994 (liquid property table, SI units).

Heater efficiency (on GCV)78.443%
Heat to the fluid2,107.5kW
Heat in the fuel2,686.7kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Coal-fired 2 MW: 25.6 kg/s, 260 to 290 °C, coal 520 kg/h at 18.6 MJ/kg. The inputs, in the units selected above:

InputValue
Thermic fluid flow92,160 kg/h
Thermic fluidEnter the properties below
Specific heat of the fluid2.6000 kJ/(kg·K)
Fluid inlet temperature260.00 °C
Fluid outlet temperature290.00 °C
Fuel flow520.00 kg/h
Gross calorific value of the fuel (as fired, per kg)18,600 kJ/kg

Applying the formula below gives:

ResultValue
Heater efficiency (on GCV)74.323 %
Heat to the fluid1,996.8 kW
Heat in the fuel2,686.7 kW

Open this example in the calculator and change any input.

Formula

\(\dot Q_{out} = \dot m\,c_p\,(T_2 - T_1) \qquad \dot Q_{in} = \dot m_f\,GCV \qquad \eta = \frac{\dot Q_{out}}{\dot Q_{in}}\)

Variables

Symbol Meaning SI unit
\(\dot m\) thermic fluid flow kg/s
\(\text{fluid}\) fluid chosen, or properties entered –
\(c_p\) fluid specific heat at the mean temperature J/(kg·K)
\(T_1\) fluid inlet temperature K
\(T_2\) fluid outlet temperature K
\(\dot m_f\) fuel flow kg/s
\(GCV\) gross calorific value, as fired, per kg J/kg
\(\eta\) heater efficiency on GCV –
\(\dot Q_{out}\) heat to the fluid W
\(\dot Q_{in}\) heat in the fuel W

Method and standards

Input–output (direct) efficiency, the same definition as for boilers, with the fluid specific heat at the mean temperature. Fluid properties: either typed in, or taken from the makers' published liquid tables for Therminol 55 (Eastman bulletin TF8994), Therminol VP-1 (Eastman bulletin TF9141), DOWTHERM A (Dow technical data sheet; no kinematic viscosity tabulated) and Therminol 66 (Eastman bulletin SFE-HTF-19853), interpolated linearly between the published points (viscosity linearly in its logarithm) and never extrapolated. More fluids will be added as their makers' tables are captured.

Where it is used

  • Energy audits of hot oil heaters.
  • Comparing fuels and heaters.
  • Tracking heater performance over time.

Common mistakes

  • Using a flow meter calibrated for cold oil.
  • Taking the specific heat at room temperature.
  • Mixing GCV and NCV.

Assumptions and limits

  • Steady load; accurate fluid flow and fuel weighing; specific heat at the mean temperature.
  • GCV and fuel flow on a mass, as-fired basis; convert gas from volume first.
  • An efficiency above 100 % is rejected as a measurement error.

References

  • Input–output (direct) method
  • as for boilers

Questions and answers

How efficient is my thermic fluid heater?

Heat to the fluid over heat in the fuel. 25.6 kg/s of oil heated from 260 to 290 °C at 2.6 kJ/(kg·K) takes 2.0 MW; burning 520 kg/h of coal at 18.6 MJ/kg supplies 2.69 MW: 74.3 % efficient.

Why are hot oil heaters often less efficient than boilers?

The fluid returns hot (250–300 °C), so the flue gas cannot be cooled much below it without an economiser or air preheater.

How do I improve it?

Add an air preheater or economiser on the flue gas, tune excess air, clean the coils, and insulate.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.