Worked example
Example: 1.25 MW connected. The inputs, in the units selected above:
| Input | Value |
|---|---|
| User 1 load | 600.00 kW |
| User 2 load | 400.00 kW |
| User 3 load | 250.00 kW |
| User 4 load | 0 kW |
| User 5 load | 0 kW |
| Diversity factor | 90.000 % |
| Piping and tank heat loss share | 5.0000 % |
| Design margin | 15.000 % |
| Fluid specific heat at mean temperature | 2.5000 kJ/(kg·K) |
| Supply–return temperature difference | 25.000 K |
Applying the formula below gives:
| Result | Value |
|---|---|
| Connected load | 1,250.0 kW |
| Demand with diversity and losses | 1,181.2 kW |
| Heater rating | 1,358.4 kW |
| Circulation flow | 78.246 t/h |
| Heater rating (lakh kcal/h) | 11.680 |
Open this example in the calculator and change any input.
Formula
\(Q_d = k_d\sum Q_i\,(1 + f_l), \quad Q_h = Q_d(1 + m), \quad \dot m = \frac{Q_h}{c_p\Delta T}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_1\) | User 1 load | W |
| \(Q_2\) | User 2 load | W |
| \(Q_3\) | User 3 load | W |
| \(Q_4\) | User 4 load | W |
| \(Q_5\) | User 5 load | W |
| \(k_d\) | Diversity factor | - |
| \(f_l\) | Piping and tank heat loss share | - |
| \(m\) | Design margin | - |
| \(c_p\) | Fluid specific heat at mean temperature | J/(kg·K) |
| \(\Delta T\) | Supply–return temperature difference | K |
| \(\Sigma Q\) | Connected load | W |
| \(Q_d\) | Demand with diversity and losses | W |
| \(Q_h\) | Heater rating | W |
| \(\dot m\) | Circulation flow | kg/s |
Method and standards
Load summation.
Where it is used
- New thermic fluid systems.
- Adding users to an existing heater.
Common mistakes
- Adding margin twice (users and heater).
- Using a ΔT larger than the users can accept.
Assumptions and limits
- Steady loads.
- Piping and tank loss is taken as a share of the diversified load. A heat loss is closer to fixed for a given system and temperature, so with a low diversity factor the loss is understated; enter a larger share then.
References
- Heat balance definitions (Q = ṁc_pΔT)
Questions and answers
Why a diversity factor?
Users rarely all draw peak load together; 0.8–0.9 is common for process plants.
Why rate heaters in lakh kcal/h?
It is the usual Indian rating; 1 lakh kcal/h is 116.3 kW.
What do the defaults give?
1.25 MW connected, 0.9 diversity, 5 % loss and 15 % margin: about 1.36 MW (11.7 lakh kcal/h) and 78 t/h of flow at 25 K.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.