Worked example
Example: Coal-fired 2 MW: 25.6 kg/s, 260 to 290 °C, coal 520 kg/h at 18.6 MJ/kg. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Thermic fluid flow | 92,160 kg/h |
| Thermic fluid | Enter the properties below |
| Specific heat of the fluid | 2.6000 kJ/(kg·K) |
| Fluid inlet temperature | 260.00 °C |
| Fluid outlet temperature | 290.00 °C |
| Fuel flow | 520.00 kg/h |
| Gross calorific value of the fuel (as fired, per kg) | 18,600 kJ/kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heater efficiency (on GCV) | 74.323 % |
| Heat to the fluid | 1,996.8 kW |
| Heat in the fuel | 2,686.7 kW |
Open this example in the calculator and change any input.
Formula
\(\dot Q_{out} = \dot m\,c_p\,(T_2 - T_1) \qquad \dot Q_{in} = \dot m_f\,GCV \qquad \eta = \frac{\dot Q_{out}}{\dot Q_{in}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | thermic fluid flow | kg/s |
| \(\text{fluid}\) | fluid chosen, or properties entered | – |
| \(c_p\) | fluid specific heat at the mean temperature | J/(kg·K) |
| \(T_1\) | fluid inlet temperature | K |
| \(T_2\) | fluid outlet temperature | K |
| \(\dot m_f\) | fuel flow | kg/s |
| \(GCV\) | gross calorific value, as fired, per kg | J/kg |
| \(\eta\) | heater efficiency on GCV | – |
| \(\dot Q_{out}\) | heat to the fluid | W |
| \(\dot Q_{in}\) | heat in the fuel | W |
Method and standards
Input–output (direct) efficiency, the same definition as for boilers, with the fluid specific heat at the mean temperature. Fluid properties: either typed in, or taken from the makers' published liquid tables for Therminol 55 (Eastman bulletin TF8994), Therminol VP-1 (Eastman bulletin TF9141), DOWTHERM A (Dow technical data sheet; no kinematic viscosity tabulated) and Therminol 66 (Eastman bulletin SFE-HTF-19853), interpolated linearly between the published points (viscosity linearly in its logarithm) and never extrapolated. More fluids will be added as their makers' tables are captured.
Where it is used
- Energy audits of hot oil heaters.
- Comparing fuels and heaters.
- Tracking heater performance over time.
Common mistakes
- Using a flow meter calibrated for cold oil.
- Taking the specific heat at room temperature.
- Mixing GCV and NCV.
Assumptions and limits
- Steady load; accurate fluid flow and fuel weighing; specific heat at the mean temperature.
- GCV and fuel flow on a mass, as-fired basis; convert gas from volume first.
- An efficiency above 100 % is rejected as a measurement error.
References
- Input–output (direct) method
- as for boilers
Questions and answers
How efficient is my thermic fluid heater?
Heat to the fluid over heat in the fuel. 25.6 kg/s of oil heated from 260 to 290 °C at 2.6 kJ/(kg·K) takes 2.0 MW; burning 520 kg/h of coal at 18.6 MJ/kg supplies 2.69 MW: 74.3 % efficient.
Why are hot oil heaters often less efficient than boilers?
The fluid returns hot (250–300 °C), so the flue gas cannot be cooled much below it without an economiser or air preheater.
How do I improve it?
Add an air preheater or economiser on the flue gas, tune excess air, clean the coils, and insulate.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.