Worked example
Example: 2 MW heater, 260 to 290 °C, c_p 2.6 kJ/(kg K), 760 kg/m³, 100 mm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Heater duty | 2,000.0 kW |
| Fluid return temperature (heater inlet) | 260.00 °C |
| Fluid supply temperature (heater outlet) | 290.00 °C |
| Thermic fluid | Enter the properties below |
| Specific heat of the fluid | 2.6000 kJ/(kg·K) |
| Density of the fluid | 760.00 kg/m³ |
| Main pipe inside diameter | 102.30 mm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fluid mass flow | 92,308 kg/h |
| Fluid volume flow | 121.46 m³/h |
| Velocity in the main pipe | 4.1047 m/s |
| Temperature difference across the heater | 30.000 K |
Open this example in the calculator and change any input.
Formula
\(\dot m = \frac{\dot Q}{c_p\,(T_2 - T_1)} \qquad \dot V = \frac{\dot m}{\rho} \qquad v = \frac{\dot V}{\pi D^2/4} \qquad \Delta T = T_2 - T_1\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q\) | heater duty | W |
| \(T_1\) | return temperature | K |
| \(T_2\) | supply temperature | K |
| \(\text{fluid}\) | fluid chosen, or properties entered | – |
| \(c_p\) | fluid specific heat at the mean temperature | J/(kg·K) |
| \(\rho\) | fluid density | kg/m³ |
| \(D\) | main pipe inside diameter | m |
| \(\dot m\) | mass flow | kg/s |
| \(\dot V\) | volume flow | m³/s |
| \(v\) | velocity | m/s |
| \(\Delta T\) | temperature difference | K |
Method and standards
Energy balance of the heater and continuity in the pipe, with properties at the mean of supply and return temperature. Fluid properties: either typed in, or taken from the makers' published liquid tables for Therminol 55 (Eastman bulletin TF8994), Therminol VP-1 (Eastman bulletin TF9141), DOWTHERM A (Dow technical data sheet; no kinematic viscosity tabulated) and Therminol 66 (Eastman bulletin SFE-HTF-19853), interpolated linearly between the published points (viscosity linearly in its logarithm) and never extrapolated. More fluids will be added as their makers' tables are captured.
Where it is used
- Sizing circulation pumps and main pipes of hot oil systems.
- Checking heater flow against the maker's minimum.
- Adding new users to an existing system.
Common mistakes
- Using the density at room temperature for the hot volume flow.
- Taking the cold specific heat: it rises with temperature.
- Ignoring the heater maker's minimum flow.
Assumptions and limits
- Properties at the mean temperature; steady duty. With "enter the properties", type c_p and ρ at the mean of supply and return temperatures.
- The pipe velocity is not checked against limits; compare it with your piping design rules.
References
- First law of thermodynamics (Q = m c_p ΔT)
- continuity
Questions and answers
How much thermic fluid must circulate?
Duty over specific heat times temperature difference. A 2 MW heater with 30 K across it and c_p = 2.6 kJ/(kg·K) needs 25.6 kg/s, about 121 m³/h at 760 kg/m³; in a pipe of 102.3 mm bore (DN100 schedule 40) that is 4.1 m/s.
What temperature difference should I use?
Usually 20–40 K across the heater. A small difference needs more flow and pump power; a large one gives low coil velocity and a hot film.
Which properties should I enter?
Choose Therminol 55, Therminol VP-1 or DOWTHERM A to use the maker's tables, or enter your own fluid's values at the mean temperature from its data sheet.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.