Worked example
Example: Bulk 290 °C, 40 kW/m², 50 mm tube, 2.5 m/s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Bulk fluid temperature | 290.00 °C |
| Heat flux at the tube inside wall | 40.000 kW/m² |
| Tube inside diameter | 50.000 mm |
| Fluid velocity in the tube | 2.5000 m/s |
| Thermic fluid | Enter the properties below |
| Density of the fluid | 760.00 kg/m³ |
| Specific heat of the fluid | 2.6000 kJ/(kg·K) |
| Thermal conductivity of the fluid | 0.10000 W/(m·K) |
| Kinematic viscosity of the fluid | 0.60000 cSt |
Applying the formula below gives:
| Result | Value |
|---|---|
| Film (inside wall) temperature | 307.98 °C |
| Film temperature rise above bulk | 17.977 K |
| Film heat transfer coefficient | 2,225.1 W/(m²·K) |
| Reynolds number | 208,333 |
| Prandtl number | 11.856 |
| Nusselt number | 1,112.5 |
Open this example in the calculator and change any input.
Formula
\(Re = \frac{v\,d_i}{\nu} \qquad Pr = \frac{\rho\,\nu\,c_p}{k} \qquad Nu = 0.023\,Re^{0.8}\,Pr^{0.4} \qquad h = \frac{Nu\,k}{d_i}\)
\(\Delta T_f = \frac{q''}{h} \qquad T_f = T_b + \Delta T_f\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_b\) | bulk fluid temperature | K |
| \(q''\) | heat flux at the inside wall | W/m² |
| \(d_i\) | tube inside diameter | m |
| \(v\) | fluid velocity | m/s |
| \(\text{fluid}\) | fluid chosen, or properties entered | – |
| \(\rho\) | density | kg/m³ |
| \(c_p\) | specific heat | J/(kg·K) |
| \(k\) | thermal conductivity | W/(m·K) |
| \(\nu\) | kinematic viscosity | m²/s |
| \(T_f\) | film temperature | K |
| \(\Delta T_f\) | film rise above bulk | K |
| \(h\) | film coefficient | W/(m²·K) |
| \(Re\) | Reynolds number | – |
| \(Pr\) | Prandtl number | – |
| \(Nu\) | Nusselt number | – |
Method and standards
Dittus–Boelter correlation for fully developed turbulent flow in smooth tubes, with the Prandtl exponent 0.4 for a fluid being heated; fluid properties at the bulk temperature. Fluid properties: either typed in, or taken from the makers' published liquid tables for Therminol 55 (Eastman bulletin TF8994), Therminol VP-1 (Eastman bulletin TF9141), DOWTHERM A (Dow technical data sheet; no kinematic viscosity tabulated) and Therminol 66 (Eastman bulletin SFE-HTF-19853), interpolated linearly between the published points (viscosity linearly in its logarithm) and never extrapolated. More fluids will be added as their makers' tables are captured. With a tabulated fluid, the film temperature is checked against the maker's maximum film temperature (Therminol 55: 335 °C; Therminol VP-1: 430 °C; Therminol 66: 375 °C).
Where it is used
- Checking heater coil design against the fluid's film temperature limit.
- Setting minimum circulation flow.
- Investigating fluid cracking and coil coking.
Common mistakes
- Using the average heat flux where the radiant section peak is much higher.
- Applying the correlation in laminar or transitional flow.
- Using the cold-oil viscosity.
Assumptions and limits
- Turbulent flow (Re above about 10 000), 0.6 < Pr < 160; uniform flux; properties at bulk temperature with no wall-viscosity correction (a source of error for viscous oils at high flux).
- Below Re 10 000 no film temperature is shown, because Dittus–Boelter would under-predict it.
- DOWTHERM A is not offered here because the maker publishes no viscosity table for it; choose "enter the properties" and type its viscosity.
References
- Dittus–Boelter correlation (Dittus and Boelter 1930, as given by McAdams)
Questions and answers
What is the film temperature of a thermic fluid?
The temperature of the oil at the tube wall, above the bulk. With bulk at 290 °C, 40 kW/m² heat flux, 50 mm tubes and 2.5 m/s, the film coefficient is 2225 W/(m²·K) and the film runs 18 K hotter, at 308 °C.
Why does it matter?
Every fluid has a maximum film temperature; above it the oil cracks and cokes, fouling the coil and shortening fluid life. Keep the film below the maker's limit with margin.
How do I lower the film temperature?
Raise the velocity in the coil, lower the heat flux (larger heater or lower firing), or keep the bulk temperature lower.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.