Thermic Fluid Circulation Flow and Velocity

Circulation flow of a thermic fluid (hot oil) heater from its duty and temperature difference, in kg/s and m³/h, with the velocity in the main pipe.

Refinery and petrochemicalChemical and fertiliserThermic fluid heatingFood, dairy and textileThermic fluid heaterPump

Inputs

Examples: 2 MW heater, 260 to 290 °C, c_p 2.6 kJ/(kg K), 760 kg/m³, 100 mm500 kW, 200 to 230 °C, 2.4, 800, 65 mm6 MW, 280 to 300 °C, 2.7, 740, 200 mmTherminol 55: 2 MW, 260 to 290 °C, 100 mmTherminol VP-1: 4 MW, 290 to 320 °C, 150 mmDOWTHERM A: 1 MW, 230 to 255 °C, 80 mm

Fluid properties (used when the fluid is "enter the properties")

Results

DOWTHERM A properties at 242.5 °C from Dow DOWTHERM A technical data sheet 176-01463 (saturated liquid table; kinematic viscosity not tabulated).

Fluid mass flow65,559kg/h
Fluid volume flow75.692m³/h
Velocity in the main pipe4.4115m/s
Temperature difference across the heater25.000K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2 MW heater, 260 to 290 °C, c_p 2.6 kJ/(kg K), 760 kg/m³, 100 mm. The inputs, in the units selected above:

InputValue
Heater duty2,000.0 kW
Fluid return temperature (heater inlet)260.00 °C
Fluid supply temperature (heater outlet)290.00 °C
Thermic fluidEnter the properties below
Specific heat of the fluid2.6000 kJ/(kg·K)
Density of the fluid760.00 kg/m³
Main pipe inside diameter102.30 mm

Applying the formula below gives:

ResultValue
Fluid mass flow92,308 kg/h
Fluid volume flow121.46 m³/h
Velocity in the main pipe4.1047 m/s
Temperature difference across the heater30.000 K

Open this example in the calculator and change any input.

Formula

\(\dot m = \frac{\dot Q}{c_p\,(T_2 - T_1)} \qquad \dot V = \frac{\dot m}{\rho} \qquad v = \frac{\dot V}{\pi D^2/4} \qquad \Delta T = T_2 - T_1\)

Variables

Symbol Meaning SI unit
\(\dot Q\) heater duty W
\(T_1\) return temperature K
\(T_2\) supply temperature K
\(\text{fluid}\) fluid chosen, or properties entered –
\(c_p\) fluid specific heat at the mean temperature J/(kg·K)
\(\rho\) fluid density kg/m³
\(D\) main pipe inside diameter m
\(\dot m\) mass flow kg/s
\(\dot V\) volume flow m³/s
\(v\) velocity m/s
\(\Delta T\) temperature difference K

Method and standards

Energy balance of the heater and continuity in the pipe, with properties at the mean of supply and return temperature. Fluid properties: either typed in, or taken from the makers' published liquid tables for Therminol 55 (Eastman bulletin TF8994), Therminol VP-1 (Eastman bulletin TF9141), DOWTHERM A (Dow technical data sheet; no kinematic viscosity tabulated) and Therminol 66 (Eastman bulletin SFE-HTF-19853), interpolated linearly between the published points (viscosity linearly in its logarithm) and never extrapolated. More fluids will be added as their makers' tables are captured.

Where it is used

  • Sizing circulation pumps and main pipes of hot oil systems.
  • Checking heater flow against the maker's minimum.
  • Adding new users to an existing system.

Common mistakes

  • Using the density at room temperature for the hot volume flow.
  • Taking the cold specific heat: it rises with temperature.
  • Ignoring the heater maker's minimum flow.

Assumptions and limits

  • Properties at the mean temperature; steady duty. With "enter the properties", type c_p and ρ at the mean of supply and return temperatures.
  • The pipe velocity is not checked against limits; compare it with your piping design rules.

References

  • First law of thermodynamics (Q = m c_p ΔT)
  • continuity

Questions and answers

How much thermic fluid must circulate?

Duty over specific heat times temperature difference. A 2 MW heater with 30 K across it and c_p = 2.6 kJ/(kg·K) needs 25.6 kg/s, about 121 m³/h at 760 kg/m³; in a pipe of 102.3 mm bore (DN100 schedule 40) that is 4.1 m/s.

What temperature difference should I use?

Usually 20–40 K across the heater. A small difference needs more flow and pump power; a large one gives low coil velocity and a hot film.

Which properties should I enter?

Choose Therminol 55, Therminol VP-1 or DOWTHERM A to use the maker's tables, or enter your own fluid's values at the mean temperature from its data sheet.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.