Turbine Governor Speed Regulation (Droop) and Load Sharing

Speed regulation of a turbine governor from no-load and full-load speeds, and how two units in parallel share a load change after a frequency change.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paper

Inputs

Examples: 60 MW at 4 % and 40 MW at 5 %, +10 MW, 50 HzEqual 4 % droops, 30 and 15 MW, +4.5 MW60 Hz, 3 % and 5 %, load rejection -20 MW

Accepted: 1 to 100 Hz
Accepted: 0.5 to 20 %
Accepted: 0.001 to 2,000 MW
Accepted: 0.5 to 20 %
Accepted: 0.001 to 2,000 MW
Accepted: -2,000 to 2,000 MW
Accepted: 9.5493 to 19,099 rpm

Results

Droop R = (N₀ − N)/N_r: the speed (frequency) falls by R of rated speed as load goes from zero to full. In parallel, units pick up a load change in proportion to rating divided by droop; equal droops share in proportion to rating. Secondary (frequency) control then restores the frequency.

Frequency change-0.20000Hz
Unit 1 load change3.0000MW
Unit 2 load change1.5000MW
Unit 1 no-load speed3,120.0rpm
Combined stiffness25.000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 60 MW at 4 % and 40 MW at 5 %, +10 MW, 50 Hz. The inputs, in the units selected above:

InputValue
Rated frequency50.000 Hz
Unit 1 droop (speed regulation)4.0000 %
Unit 1 rating60.000 MW
Unit 2 droop5.0000 %
Unit 2 rating40.000 MW
Load increase on the pair10.000 MW
Rated speed (for no-load and full-load speeds)3,000.0 rpm

Applying the formula below gives:

ResultValue
Frequency change-0.21739 Hz
Unit 1 load change6.5217 MW
Unit 2 load change3.4783 MW
Unit 1 no-load speed3,120.0 rpm
Combined stiffness23.000

Open this example in the calculator and change any input.

Formula

\(R = \frac{N_0 - N}{N_r}, \quad \Delta P_i = \frac{P_{r,i}}{R_if_n}(-\Delta f), \quad \Delta f = -\frac{\Delta P_L}{\sum_i P_{r,i}/(R_if_n)}\)

Variables

Symbol Meaning SI unit
\(f_n\) Rated frequency 1/s
\(R_1\) Unit 1 droop (speed regulation) -
\(P_{r1}\) Unit 1 rating W
\(R_2\) Unit 2 droop -
\(P_{r2}\) Unit 2 rating W
\(\Delta P_L\) Load increase on the pair W
\(N_r\) Rated speed (for no-load and full-load speeds) rad/s
\(\Delta f\) Frequency change 1/s
\(\Delta P_1\) Unit 1 load change W
\(\Delta P_2\) Unit 2 load change W
\(N_0\) Unit 1 no-load speed rad/s
\(\beta\) Combined stiffness -

Method and standards

Linear governor droop characteristics.

Where it is used

  • Setting governor droops for parallel operation.
  • Islanded captive plants sharing load.

Common mistakes

  • Entering droop as a percentage of frequency in Hz.
  • Ignoring that isochronous units take the whole change.

Assumptions and limits

  • Linear droop; no load frequency sensitivity; steady state.

Questions and answers

Why do units with lower droop take more load?

A smaller droop means a stiffer machine: for the same frequency drop it must open its valves further.

What do the defaults represent?

A 60 MW unit at 4 % droop and a 40 MW unit at 5 % droop on a 50 Hz system take 10 MW more load: frequency falls 0.22 Hz; the 60 MW unit takes 6.5 MW and the 40 MW unit 3.5 MW.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Nag, Power Plant Engineering, 3rd ed. (Tata McGraw-Hill, 2008), sec. 7.4, eq. 7.98 (steady-state speed regulation)

Related calculators