Worked example
Example: 60 MW at 4 % and 40 MW at 5 %, +10 MW, 50 Hz. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated frequency | 50.000 Hz |
| Unit 1 droop (speed regulation) | 4.0000 % |
| Unit 1 rating | 60.000 MW |
| Unit 2 droop | 5.0000 % |
| Unit 2 rating | 40.000 MW |
| Load increase on the pair | 10.000 MW |
| Rated speed (for no-load and full-load speeds) | 3,000.0 rpm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Frequency change | -0.21739 Hz |
| Unit 1 load change | 6.5217 MW |
| Unit 2 load change | 3.4783 MW |
| Unit 1 no-load speed | 3,120.0 rpm |
| Combined stiffness | 23.000 |
Open this example in the calculator and change any input.
Formula
\(R = \frac{N_0 - N}{N_r}, \quad \Delta P_i = \frac{P_{r,i}}{R_if_n}(-\Delta f), \quad \Delta f = -\frac{\Delta P_L}{\sum_i P_{r,i}/(R_if_n)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(f_n\) | Rated frequency | 1/s |
| \(R_1\) | Unit 1 droop (speed regulation) | - |
| \(P_{r1}\) | Unit 1 rating | W |
| \(R_2\) | Unit 2 droop | - |
| \(P_{r2}\) | Unit 2 rating | W |
| \(\Delta P_L\) | Load increase on the pair | W |
| \(N_r\) | Rated speed (for no-load and full-load speeds) | rad/s |
| \(\Delta f\) | Frequency change | 1/s |
| \(\Delta P_1\) | Unit 1 load change | W |
| \(\Delta P_2\) | Unit 2 load change | W |
| \(N_0\) | Unit 1 no-load speed | rad/s |
| \(\beta\) | Combined stiffness | - |
Method and standards
Linear governor droop characteristics.
Where it is used
- Setting governor droops for parallel operation.
- Islanded captive plants sharing load.
Common mistakes
- Entering droop as a percentage of frequency in Hz.
- Ignoring that isochronous units take the whole change.
Assumptions and limits
- Linear droop; no load frequency sensitivity; steady state.
Questions and answers
Why do units with lower droop take more load?
A smaller droop means a stiffer machine: for the same frequency drop it must open its valves further.
What do the defaults represent?
A 60 MW unit at 4 % droop and a 40 MW unit at 5 % droop on a 50 Hz system take 10 MW more load: frequency falls 0.22 Hz; the 60 MW unit takes 6.5 MW and the 40 MW unit 3.5 MW.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Nag, Power Plant Engineering, 3rd ed. (Tata McGraw-Hill, 2008), sec. 7.4, eq. 7.98 (steady-state speed regulation)