Gas Turbine Equivalent Operating Hours and Inspection Due

Equivalent operating hours from fired hours, starts, trips and peak-load hours with user weighting factors, and the time to the next inspection at the present duty.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Illustrative 18000 h, 250 startsPeaker with many startsBase-load unit, overdue

Accepted: 0 to 300,000
Accepted: 0 to 100,000
Accepted: 0 to 100
Accepted: 0 to 10,000
Accepted: 0 to 2,000
Accepted: 0 to 100,000
Accepted: 1 to 10
Accepted: 1,000 to 200,000
Accepted: 1 to 8,784
Accepted: 0 to 2,000

Results

EOH = OH + k_s·N_s + k_t·N_t + (f_p − 1)·h_p: each start, trip and peak-load hour consumes hot-section life like extra running hours. The factors and the interval are the maker's, and some makers count starts and hours separately instead. Negative remaining EOH means the inspection is overdue (years then shows 0).

Equivalent operating hours26,600
Remaining to inspection-2,600.0
Years to inspection at present duty (no trips or peak)0
Share of EOH from starts4.5113%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 18000 h, 250 starts. The inputs, in the units selected above:

InputValue
Fired operating hours18,000 -
Starts250.00 -
Equivalent hours per start20.000 -
Trips from high load6.0000 -
Equivalent hours per trip100.00 -
Hours at peak load300.00 -
Peak-load life factor3.0000 -
Inspection interval24,000 -
Fired hours per year6,000.0 -
Starts per year80.000 -

Applying the formula below gives:

ResultValue
Equivalent operating hours24,200
Remaining to inspection-200.00
Years to inspection at present duty (no trips or peak)0
Share of EOH from starts20.661 %

Open this example in the calculator and change any input.

Formula

\(EOH = OH + k_sN_s + k_tN_t + (f_p - 1)h_p\)

Variables

Symbol Meaning SI unit
\(OH\) Fired operating hours -
\(N_s\) Starts -
\(k_s\) Equivalent hours per start -
\(N_t\) Trips from high load -
\(k_t\) Equivalent hours per trip -
\(h_p\) Hours at peak load -
\(f_p\) Peak-load life factor -
\(EOH_i\) Inspection interval -
\(h_y\) Fired hours per year -
\(s_y\) Starts per year -
\(EOH\) Equivalent operating hours -
\(EOH_{rem}\) Remaining to inspection -
\(t_{insp}\) Years to inspection at present duty (no trips or peak) -
\(\frac{k_sN_s}{EOH}\) Share of EOH from starts -

Method and standards

Equivalent hours.

Where it is used

  • Outage planning for gas turbines.
  • Valuing cycling versus base-load operation.

Common mistakes

  • Using factors from a different model.
  • Forgetting trips from high load.

Assumptions and limits

  • Linear damage accumulation; constant future duty.

References

  • Equivalent operating hours concept

Questions and answers

Why do starts count as hours?

Each start and stop drives a thermal cycle that consumes low-cycle fatigue life in hot parts.

Where do the factors come from?

From the gas turbine maker's maintenance rules for that model; the defaults are only illustrative.

What do the defaults represent?

An illustrative unit with 18,000 fired hours, 250 starts (20 h each), 6 trips (100 h each) and 300 peak hours (factor 3), against a 24,000 EOH interval.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Boyce, Gas Turbine Engineering Handbook, 4th ed. (Butterworth-Heinemann, 2012), Kehlhofer, Hannemann, Stirnimann and Rukes, Combined-Cycle Gas and Steam Turbine Power Plants, 3rd ed. (PennWell, 2009)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.