Worked example
Example: DN150, 60 m run, carbon steel 12 µm/m·K, 200 K rise. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pipe outside diameter | 168.30 mm |
| Straight run between anchors | 60.000 m |
| Mean coefficient of thermal expansion | 12.000 µm/(m·K) |
| Temperature change from installation | 200.00 K |
| Modulus of elasticity | 200.00 GPa |
| Allowed displacement stress range (your design value) | 150.00 MPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Thermal growth of the run | 144.00 mm |
| Leg length to take all the growth (L-bend or Z-bend) | 9.8459 m |
| Length of each of the two legs of a U-loop at mid-run | 6.9621 m |
Open this example in the calculator and change any input.
Formula
\(\Delta = \alpha\, \Delta T\, L_r\)
\(L = \sqrt{\frac{3 E D_o \Delta}{S_A}}, \quad L_{loop} = \sqrt{\frac{3 E D_o (\Delta/2)}{S_A}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D_o\) | Pipe outside diameter | m |
| \(L_r\) | Straight run between anchors | m |
| \(\alpha\) | Mean coefficient of thermal expansion | 1/K |
| \(\Delta T\) | Temperature change from installation | K |
| \(E\) | Modulus of elasticity | Pa |
| \(S_A\) | Allowed displacement stress range (your design value) | Pa |
| \(\Delta\) | Thermal growth of the run | m |
| \(L\) | Leg length to take all the growth (L-bend or Z-bend) | m |
| \(L_{loop}\) | Length of each of the two legs of a U-loop at mid-run | m |
Method and standards
The guided cantilever method treats each leg perpendicular to the growth as a beam fixed against rotation at both ends; the bending stress for the imposed deflection must stay within the allowed displacement stress range.
Where it is used
- Laying out steam, condensate and hot water mains.
- Checking whether an L-bend can absorb growth instead of a bellows.
- Locating anchors and guides.
Common mistakes
- Using the hot temperature instead of the change from installation.
- Leaving guides too close to the loop.
- Ignoring cold pull or pre-spring when it is used.
Assumptions and limits
- Guided cantilever; bend flexibility ignored (conservative).
- Allowed stress range from your code.
- The U-loop result is the length of each leg only; the loop width (the run between the legs) and stress intensification at the bends are not considered.
References
- Guided cantilever method (M.W. Kellogg, Design of Piping Systems)
Questions and answers
What loop does a 60 m DN150 steam line need for 200 K?
It grows 144 mm. One leg taking all of it needs 9.8 m; a U-loop at mid-run with two legs of 7.0 m shares it.
Where does the formula come from?
A leg held parallel at both ends bends like a guided cantilever: Δ = S L²/(3 E D), so L = √(3 E D Δ / S).
Is this enough for design?
For utility lines it is a common quick check; critical lines need a flexibility analysis to your piping code.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.