Fan Motor Rating (kW with Margin and Cold Start)

Motor rating for a fan: power absorbed plus the motor margin, rounded to the next IEC standard rating, and the power when started on cold air.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationThermic fluid heatingFan and blowerElectric motor

Inputs

Examples: FD fan 20 m³/s, 3 kPa, 80 %, +10 %ID fan 45 m³/s, 2.75 kPa at 140 °C, cold start 30 °CShaft power 130 kW entered, hot gas 160 °C, cold 20 °C

10 % for fan motors. Default from FireCAD design practice; enter your specification's value.

Flow, pressure and efficiency

From the fan maker at the duty point. Default from FireCAD design practice; enter your specification's value.

Shaft power entered

Cold start

Air 28.97; flue gas about 30 (coal, oil) or 27.5–28.5 (natural gas).

Results

On cold air the fan needs more than the motor sized for the duty: start with dampers or vanes closed, use a variable speed drive, or take the larger rating.

Standard motor rating (IEC 60072-1)200.00kW
Minimum motor rating (absorbed + margin)170.16kW
Power absorbed at the duty point154.69kW
Power on cold air at the same speed and flow203.55kW
Standard rating that also covers the cold start250.00kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: FD fan 20 m³/s, 3 kPa, 80 %, +10 %. The inputs, in the units selected above:

InputValue
Power absorbed fromFlow, pressure and efficiency
Volume flow at the fan inlet72,000 m³/h
Fan pressure305.91 mmWC
Fan efficiency80.000 %
Fan shaft power (from the maker's data)0 kW
Motor margin over the power absorbed10.000 %
Gas temperature at the duty point35.000 °C
Molar mass of the gas at the duty point28.966 kg/kmol
Air temperature at a cold start35.000 °C

Applying the formula below gives:

ResultValue
Standard motor rating (IEC 60072-1)90.000 kW
Minimum motor rating (absorbed + margin)82.500 kW
Power absorbed at the duty point75.000 kW
Power on cold air at the same speed and flow75.000 kW
Standard rating that also covers the cold start90.000 kW

Open this example in the calculator and change any input.

Formula

\(P_s = \frac{\dot V\,\Delta p}{\eta_f}\ \ (\text{or } P_{s,in}) \qquad P_{m,min} = P_s(1 + m_m) \qquad P_c = P_s\,\frac{M_{da}/T_c}{M_h/T_h}\)

\(P_{std}\) is the next IEC 60072-1 rating at or above \(P_{m,min}\); \(P_{std,c}\) the next at or above the larger of \(P_{m,min}\) and \(P_c\).

Variables

Symbol Meaning SI unit
\(\text{basis}\) power from flow and pressure, or shaft power entered –
\(\dot V\) volume flow at the fan inlet m³/s
\(\Delta p\) fan pressure Pa
\(\eta_f\) fan efficiency –
\(P_{s,in}\) shaft power from the maker's data W
\(m_m\) motor margin –
\(T_h\) gas temperature at the duty point K
\(M_h\) molar mass of the gas at the duty point kg/kmol
\(T_c\) air temperature at a cold start K
\(P_{std}\) standard motor rating W
\(P_{m,min}\) minimum motor rating W
\(P_s\) power absorbed at the duty point W
\(P_c\) power on cold air at the same speed and flow W
\(P_{std,c}\) standard rating that also covers the cold start W
\(M_{da}\) molar mass of dry air kg/kmol

Method and standards

Fan power per ISO 5801; cold-start power by the AMCA 99 fan laws at constant speed and volume (power in proportion to density, ideal gas at the same pressure); ratings from IEC 60072-1. Default efficiency and margin are FireCAD design practice (owner, 2026-11-10).

Where it is used

  • Selecting FD, ID and PA fan motors.
  • Checking motor size after a fan modification.
  • Specifying motors for purchase.

Common mistakes

  • Sizing on hot-gas power when the fan starts on cold air.
  • Adding margins twice.
  • Ignoring drive (belt or coupling) losses.

Assumptions and limits

  • Same inlet pressure hot and cold.
  • Fan pressure and efficiency on one basis (total with total efficiency, or static with static efficiency).
  • No separate drive efficiency: for a belt or fluid-coupling drive divide the fan shaft power by the drive efficiency, or allow for it in the motor margin.
  • Starting torque, acceleration time and the motor's thermal limits during a damper-closed start are not checked here.

References

  • ISO 5801 (fan power)
  • AMCA 99 (fan laws)
  • IEC 60072-1 (standard motor ratings)

Questions and answers

How do I select a motor for a fan?

Power absorbed plus the motor margin, rounded up to the next standard rating. An FD fan of 20 m³/s at 3 kPa and 80 % absorbs 75 kW; with 10 % margin it needs 82.5 kW, so a 90 kW motor.

Why check the cold start?

A hot-gas fan started on cold air at full speed with dampers open absorbs power in proportion to density. An ID fan absorbing 155 kW at 140 °C would take 204 kW on 30 °C air, more than its 200 kW motor.

Why 10 %?

It is the FireCAD design-practice default for fan motors; your specification may set another margin.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.