Worked example
Example: FD fan 20 m³/s, 3 kPa, 80 %, +10 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Power absorbed from | Flow, pressure and efficiency |
| Volume flow at the fan inlet | 72,000 m³/h |
| Fan pressure | 305.91 mmWC |
| Fan efficiency | 80.000 % |
| Fan shaft power (from the maker's data) | 0 kW |
| Motor margin over the power absorbed | 10.000 % |
| Gas temperature at the duty point | 35.000 °C |
| Molar mass of the gas at the duty point | 28.966 kg/kmol |
| Air temperature at a cold start | 35.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Standard motor rating (IEC 60072-1) | 90.000 kW |
| Minimum motor rating (absorbed + margin) | 82.500 kW |
| Power absorbed at the duty point | 75.000 kW |
| Power on cold air at the same speed and flow | 75.000 kW |
| Standard rating that also covers the cold start | 90.000 kW |
Open this example in the calculator and change any input.
Formula
\(P_s = \frac{\dot V\,\Delta p}{\eta_f}\ \ (\text{or } P_{s,in}) \qquad P_{m,min} = P_s(1 + m_m) \qquad P_c = P_s\,\frac{M_{da}/T_c}{M_h/T_h}\)
\(P_{std}\) is the next IEC 60072-1 rating at or above \(P_{m,min}\); \(P_{std,c}\) the next at or above the larger of \(P_{m,min}\) and \(P_c\).
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{basis}\) | power from flow and pressure, or shaft power entered | – |
| \(\dot V\) | volume flow at the fan inlet | m³/s |
| \(\Delta p\) | fan pressure | Pa |
| \(\eta_f\) | fan efficiency | – |
| \(P_{s,in}\) | shaft power from the maker's data | W |
| \(m_m\) | motor margin | – |
| \(T_h\) | gas temperature at the duty point | K |
| \(M_h\) | molar mass of the gas at the duty point | kg/kmol |
| \(T_c\) | air temperature at a cold start | K |
| \(P_{std}\) | standard motor rating | W |
| \(P_{m,min}\) | minimum motor rating | W |
| \(P_s\) | power absorbed at the duty point | W |
| \(P_c\) | power on cold air at the same speed and flow | W |
| \(P_{std,c}\) | standard rating that also covers the cold start | W |
| \(M_{da}\) | molar mass of dry air | kg/kmol |
Method and standards
Fan power per ISO 5801; cold-start power by the AMCA 99 fan laws at constant speed and volume (power in proportion to density, ideal gas at the same pressure); ratings from IEC 60072-1. Default efficiency and margin are FireCAD design practice (owner, 2026-11-10).
Where it is used
- Selecting FD, ID and PA fan motors.
- Checking motor size after a fan modification.
- Specifying motors for purchase.
Common mistakes
- Sizing on hot-gas power when the fan starts on cold air.
- Adding margins twice.
- Ignoring drive (belt or coupling) losses.
Assumptions and limits
- Same inlet pressure hot and cold.
- Fan pressure and efficiency on one basis (total with total efficiency, or static with static efficiency).
- No separate drive efficiency: for a belt or fluid-coupling drive divide the fan shaft power by the drive efficiency, or allow for it in the motor margin.
- Starting torque, acceleration time and the motor's thermal limits during a damper-closed start are not checked here.
References
- ISO 5801 (fan power)
- AMCA 99 (fan laws)
- IEC 60072-1 (standard motor ratings)
Questions and answers
How do I select a motor for a fan?
Power absorbed plus the motor margin, rounded up to the next standard rating. An FD fan of 20 m³/s at 3 kPa and 80 % absorbs 75 kW; with 10 % margin it needs 82.5 kW, so a 90 kW motor.
Why check the cold start?
A hot-gas fan started on cold air at full speed with dampers open absorbs power in proportion to density. An ID fan absorbing 155 kW at 140 °C would take 204 kW on 30 °C air, more than its 200 kW motor.
Why 10 %?
It is the FireCAD design-practice default for fan motors; your specification may set another margin.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.