Interface Level by Differential Pressure

Height of the interface between two immiscible liquids from a DP transmitter between two taps, with the transmitter range for interface at the lower and upper tap.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Taps 2 m apart, oil 850 / water 1 000, 181 mbarDesalter 1.5 m, crude 880 / brine 1 050, 140 mbarCondensate 700 / water 1 000, 1 m, interface at 30 %

Results

Both taps must stay covered by liquid; filled or sealed impulse lines add their own head, removed by zero suppression.

DP with interface at the lower tap (all light)166.71mbar
DP with interface at the upper tap (all heavy)196.13mbar
Interface height above the lower tap0.97124m
Interface level as a share of the range48.562%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Taps 2 m apart, oil 850 / water 1 000, 181 mbar. The inputs, in the units selected above:

InputValue
Distance between the taps2.0000 m
Density of the lighter liquid (top)850.00 kg/m³
Density of the heavier liquid (bottom)1,000.0 kg/m³
Measured DP (with the taps fully covered)181.00 mbar

Applying the formula below gives:

ResultValue
DP with interface at the lower tap (all light)166.71 mbar
DP with interface at the upper tap (all heavy)196.13 mbar
Interface height above the lower tap0.97124 m
Interface level as a share of the range48.562 %

Open this example in the calculator and change any input.

Formula

\(\Delta p = g\,[\rho_H h_i + \rho_L (H - h_i)], \quad h_i = \frac{\Delta p - \rho_L g H}{(\rho_H - \rho_L) g}\)

Variables

Symbol Meaning SI unit
\(H\) Distance between the taps m
\(\rho_L\) Density of the lighter liquid (top) kg/m³
\(\rho_H\) Density of the heavier liquid (bottom) kg/m³
\(\Delta p\) Measured DP (with the taps fully covered) Pa
\(\Delta p_0\) DP with interface at the lower tap (all light) Pa
\(\Delta p_1\) DP with interface at the upper tap (all heavy) Pa
\(h_i\) Interface height above the lower tap m
\(h_i/H\) Interface level as a share of the range -

Method and standards

Hydrostatics of two layers.

Where it is used

  • Separators, settlers and desalters.
  • Transmitter ranging.

Common mistakes

  • Ignoring impulse-line fill.
  • Density changes with temperature.

Assumptions and limits

  • Both taps covered; clear interface.

References

  • Hydrostatics
  • Δp = g (ρ_H h + ρ_L (H − h))

Questions and answers

What range for taps 2 m apart, oil 850 and water 1000 kg/m³?

166.7 to 196.1 mbar: a narrow span of 29.4 mbar.

Why is interface DP hard?

The span depends on the density difference, which is small and varies.

What if the top liquid drops below the upper tap?

The reading is wrong; total level must stay above the upper tap.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.