DP Level Transmitter Range (LRV, URV, Wet Leg)

Lower and upper range values of a differential pressure level transmitter for an open tank or a closed tank with a wet (filled) reference leg.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserBoilerTank and drum

Inputs

Examples: Closed tank, wet leg: span 2 m, zero 0.3 m, leg 2.5 m, water 1000 / 1000Open oil tank: span 6 m, zero 0.2 m, 860 kg/m³Wet leg with glycol: span 1.5 m, zero 0, leg 1.8 m, process 950, leg 1100

Results

With a wet leg the range is usually negative (suppressed or elevated zero); this is normal.

Lower range value-1,980.0mmWC
Upper range value-555.00mmWC
Calibrated span1,425.0mmWC

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Closed tank, wet leg: span 2 m, zero 0.3 m, leg 2.5 m, water 1000 / 1000. The inputs, in the units selected above:

InputValue
Level span to measure2.0000 m
Lowest level to measure, above the lower (high-side) tap0.30000 m
Low-side connectionWet (filled) reference leg
Wet leg height above the lower tap2.5000 m
Process liquid density1,000.0 kg/m³
Wet leg fill density1,000.0 kg/m³

Applying the formula below gives:

ResultValue
Lower range value-2,200.0 mmWC
Upper range value-200.00 mmWC
Calibrated span2,000.0 mmWC

Open this example in the calculator and change any input.

Formula

\(LRV = \rho_p g h_0 - \rho_l g H \qquad URV = \rho_p g (h_0 + h_s) - \rho_l g H \qquad \Delta p_s = URV - LRV\)

Variables

Symbol Meaning SI unit
\(h_s\) level span m
\(h_0\) lowest level above lower tap m
\(\text{leg}\) dry/open or wet leg –
\(H\) wet leg height m
\(\rho_p\) process density kg/m³
\(\rho_l\) leg fill density kg/m³
\(LRV\) lower range value Pa
\(URV\) upper range value Pa
\(\Delta p_s\) span Pa
\(g\) standard gravity m/s²

Method and standards

Hydrostatic heads of the process and reference legs; the high side connected to the lower tap.

Where it is used

  • Calibrating level transmitters on tanks and vessels.
  • Choosing between dry and wet legs.
  • Commissioning checks.

Common mistakes

  • Using water density for other liquids.
  • Forgetting the transmitter's mounting height below the tap.
  • Leaving a wet leg partly empty.

Assumptions and limits

  • Constant densities; legs fully filled or empty as chosen.
  • The vapour or gas density above the liquid is neglected. For boiler drums, where steam density matters, use the drum level DP compensation calculator.

References

  • Hydrostatics of the process and reference legs

Questions and answers

How do I range a DP level transmitter with a wet leg?

For water level from 0.3 m to 2.3 m above the lower tap with a 2.5 m water-filled wet leg, LRV is −2200 mmWC and URV −200 mmWC: a 2000 mmWC span below zero.

Why are the values negative?

The wet leg's head on the low side is larger than the process head; this zero elevation is normal.

Open tank?

With the low side vented, LRV and URV are just the process heads at the two levels.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.