Worked example
Example: 12 mm rod in 50 mm tube, 2 m, oil 2.2, half full. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rod (inner electrode) diameter | 12.000 mm |
| Tube or vessel inside diameter (outer electrode) | 50.000 mm |
| Active length | 2.0000 m |
| Dielectric constant of the liquid | 2.2000 - |
| Level on the probe | 1.0000 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Capacitance empty | 77.965 pF |
| Capacitance full | 171.52 pF |
| Capacitance at the level | 124.74 pF |
| Capacitance change for 1 m of level | 46.779 pF |
Open this example in the calculator and change any input.
Formula
\(C' = \frac{2\pi\varepsilon_0}{\ln(D/d)}, \quad C_h = C'\,[\varepsilon_r h + (L - h)], \quad \Delta C_{1m} = C'(\varepsilon_r - 1)\times 1\ \mathrm{m}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(d\) | Rod (inner electrode) diameter | m |
| \(D\) | Tube or vessel inside diameter (outer electrode) | m |
| \(L\) | Active length | m |
| \(\varepsilon_r\) | Dielectric constant of the liquid | - |
| \(h\) | Level on the probe | m |
| \(C_0\) | Capacitance empty | F |
| \(C_1\) | Capacitance full | F |
| \(C_h\) | Capacitance at the level | F |
| \(\Delta C_{1m}\) | Capacitance change for 1 m of level | F |
| \(C'\) | Capacitance per metre of probe in air, 2πε₀/ln(D/d) | F/m |
Method and standards
Coaxial capacitor with a partly filled gap.
Where it is used
- Probe selection.
- Level switch set-up.
Common mistakes
- Using it for conductive liquids uninsulated.
- Coating on the probe.
Assumptions and limits
- Concentric electrodes.
References
- Capacitance of a coaxial capacitor
- C = 2π ε₀ ε_r L / ln(D/d)
Questions and answers
What does a 12 mm rod in a 50 mm tube, 2 m long, give in oil (ε_r 2.2)?
Empty 78 pF, full 172 pF.
Why are oils hard?
A low dielectric constant gives a small change.
What about water?
It conducts, so the rod must be insulated.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.