Bubbler (Dip-Tube) Level and Density Measurement

Liquid level above a bubbler dip-tube from the back pressure and liquid density, and the liquid density from two dip-tubes at different depths.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Two tubes 1 m apart, water-likeMolasses 1,400 kg/m³, tubes 0.5 m apart

Results

Back pressure equals the liquid head at the tube end once the purge just bubbles. Keep purge flow small so line friction is negligible; vented tanks need gauge pressures.

Liquid level above the lower tube2.9135m
Level above tank bottom3.0635m
Measured density (two tubes)1,407.2kg/m³
Level using the measured density3.0486m

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Two tubes 1 m apart, water-like. The inputs, in the units selected above:

InputValue
Back pressure, lower tube (gauge)25.000 kPa
Back pressure, upper tube (gauge)15.200 kPa
Vertical distance between tube ends1.0000 m
Liquid density (for level from one tube)1,000.0 kg/m³
Height of the lower tube end above tank bottom0.10000 m

Applying the formula below gives:

ResultValue
Liquid level above the lower tube2.5493 m
Level above tank bottom2.6493 m
Measured density (two tubes)999.32 kg/m³
Level using the measured density2.6510 m

Open this example in the calculator and change any input.

Formula

\(h = \frac{p_1}{\rho g}, \quad \rho_m = \frac{p_1 - p_2}{g\,\Delta h}\)

Variables

Symbol Meaning SI unit
\(p_1\) Back pressure, lower tube (gauge) Pa
\(p_2\) Back pressure, upper tube (gauge) Pa
\(\Delta h\) Vertical distance between tube ends m
\(\rho\) Liquid density (for level from one tube) kg/m³
\(z_1\) Height of the lower tube end above tank bottom m
\(h\) Liquid level above the lower tube m
\(L\) Level above tank bottom m
\(\rho_m\) Measured density (two tubes) kg/m³
\(h_{\rho m}\) Level using the measured density m

Method and standards

Hydrostatics.

Where it is used

  • Molasses, acid and slurry tanks.
  • Density of process liquids.

Common mistakes

  • Large purge flow adding line friction.
  • Using absolute pressures in a vented tank.

Assumptions and limits

  • Static liquid; negligible purge friction.
  • Both tube ends must be submerged for the density; an uncovered upper tube (zero back pressure, or a level below it) is flagged.

References

  • Hydrostatics of purged dip tubes (definitions; Lipták, Instrument Engineers' Handbook, 4th ed. (CRC Press), vol. 1, level)

Questions and answers

Why use bubblers?

Only the dip tube touches the liquid: good for corrosive, hot, slurry or crystallising liquids such as molasses, spent wash and acids.

How do two tubes give density?

The difference in back pressure over a known vertical spacing is ρgΔh, independent of level.

What do the defaults represent?

Two dip tubes 1 m apart in a water-like liquid.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.