FireCADCalc

Control Valve Characteristic: Flow at an Opening

Relative flow coefficient of a control valve at a travel for linear, equal-percentage and quick-opening characteristics, with the Cv at that opening.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Half open, R 50, Cv 10020 % open, R 30, Cv 25Full open, R 50, Cv 160

Results

Inherent characteristics at constant DP; installed characteristics differ with valve authority. Real quick-opening trims vary by maker.

Linear: share of rated Cv20.000%
Equal percentage: share of rated Cv R^(x−1)6.5812%
Quick opening (square-root form): share of rated Cv44.721%
Cv, linear5.0000
Cv, equal percentage1.6453

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Half open, R 50, Cv 100. The inputs, in the units selected above:

InputValue
Valve travel (opening)50.000 %
Inherent rangeability (equal percentage)50.000 -
Rated Cv at full travel100.00 -

Applying the formula below gives:

ResultValue
Linear: share of rated Cv50.000 %
Equal percentage: share of rated Cv R^(x−1)14.142 %
Quick opening (square-root form): share of rated Cv70.711 %
Cv, linear50.000
Cv, equal percentage14.142

Open this example in the calculator and change any input.

Formula

\(f_{lin} = x, \quad f_{eq} = R^{x-1}, \quad f_{qo} = \sqrt x\)

Variables

Symbol Meaning SI unit
\(x\) Valve travel (opening) -
\(R\) Inherent rangeability (equal percentage) -
\(C_{v,max}\) Rated Cv at full travel -
\(f_{lin}\) Linear: share of rated Cv -
\(f_{eq}\) Equal percentage: share of rated Cv R^(x−1) -
\(f_{qo}\) Quick opening (square-root form): share of rated Cv -
\(C_{v,lin}\) Cv, linear -
\(C_{v,eq}\) Cv, equal percentage -

Method and standards

Inherent characteristics.

Where it is used

  • Valve selection and control loop gain.
  • Checking a valve's position against flow.

Common mistakes

  • Confusing inherent and installed curves.
  • Using equal percentage at very low travel.

Assumptions and limits

  • The ideal equal-percentage curve gives 1/R of rated Cv at zero travel, not zero: a real valve departs from the curve below its rangeability limit and shuts off at the seat.

  • Constant DP across the valve.

References

  • Inherent flow characteristics (IEC 60534-2-4; ISA-75.11.01)

Questions and answers

What Cv at half travel, R = 50?

Linear 50 % of Cv; equal percentage 14.1 %.

Why equal percentage?

Each step in travel changes flow by the same percentage: it compensates for falling DP in most systems.

Is the equal-percentage curve zero at closed?

No, it gives 1/R; real valves shut off below that.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.