Control Valve Authority

Authority of a control valve from its pressure drop and the rest of the circuit's, with the installed flow at an opening for a linear or equal-percentage valve.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 30 kPa valve, 70 kPa circuit, half open, R 50Good authority 0.5, 30 % openPoor authority 0.1, 50 % open

Results

Authority below 0.25: most of the travel changes the flow little and the last part a lot, so control is poor. Increase the valve's share of the pressure drop (smaller valve) if the pump allows.

Installed flow with a constant total pressure difference. Authority of at least 0.25 (0.5 is often preferred in HVAC) is common design practice, not a code limit.

Valve authority Δp_v / (Δp_v + Δp_s)10.000%
Installed flow share, linear valve87.706%
Installed flow share, equal-percentage valve50.637%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 30 kPa valve, 70 kPa circuit, half open, R 50. The inputs, in the units selected above:

InputValue
Pressure drop across the fully open valve30.000 kPa
Pressure drop in the rest of the circuit at design flow70.000 kPa
Valve travel50.000 %
Rangeability (equal percentage)50.000 -

Applying the formula below gives:

ResultValue
Valve authority Δp_v / (Δp_v + Δp_s)30.000 %
Installed flow share, linear valve72.548 %
Installed flow share, equal-percentage valve25.238 %

Open this example in the calculator and change any input.

Formula

\(N = \frac{\Delta p_v}{\Delta p_v + \Delta p_s}, \quad q = \frac{1}{\sqrt{N/f^2 + (1 - N)}}\)

Variables

Symbol Meaning SI unit
\(\Delta p_v\) Pressure drop across the fully open valve Pa
\(\Delta p_s\) Pressure drop in the rest of the circuit at design flow Pa
\(x\) Valve travel -
\(R\) Rangeability (equal percentage) -
\(N\) Valve authority Δp_v / (Δp_v + Δp_s) -
\(q_{lin}\) Installed flow share, linear valve -
\(q_{eq}\) Installed flow share, equal-percentage valve -

Method and standards

Valve and circuit resistances in series.

Where it is used

  • HVAC and process valve selection.
  • Diagnosing poor control.

Common mistakes

  • Using the valve DP at part load.
  • Oversized valves.

Assumptions and limits

  • The 0.25 lower limit flagged on the page is a common rule of thumb for acceptable control (many HVAC designers aim for 0.5); it is practice, not a figure from a standard.

  • Constant total ΔP.

References

  • Valve authority and installed characteristic (CIBSE Guide H; series flow resistance)

Questions and answers

30 kPa across the valve, 70 kPa in the rest?

Authority 0.3.

What flow at half travel?

Linear valve 73 % of full flow; equal percentage 25 %.

Why does authority matter?

With low authority most of the travel does little, then flow rises sharply near full open.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.