Control Valve Characteristic, Authority and Installed Flow

Inherent and installed flow of a linear or equal-percentage control valve at a given opening, from rangeability and valve authority, with the installed gain.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPump

Inputs

Examples: Equal %, R 50, 50 % open, authority 0.3Linear, 70 % open, authority 0.2Equal %, R 30, 80 % open, authority 0.5

Results

Authority below about 0.25 (a common design rule of thumb, not a standard limit): the installed characteristic is badly distorted and control at high flow will be poor.

Inherent relative flow (at constant Δp)70.000%
Installed relative flow (share of full-open flow)90.978%
Installed gain0.43908
Installed flow at the least controllable opening4.4686%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Equal %, R 50, 50 % open, authority 0.3. The inputs, in the units selected above:

InputValue
Inherent characteristicEqual percentage
Valve travel (opening)50.000 %
Inherent rangeability (largest to least controllable flow)50.000 -
Valve authority (valve Δp fully open ÷ system Δp)30.000 %

Applying the formula below gives:

ResultValue
Inherent relative flow (at constant Δp)14.142 %
Installed relative flow (share of full-open flow)25.238 %
Installed gain0.94329
Installed flow at the least controllable opening3.6498 %

Open this example in the calculator and change any input.

Formula

\(\varphi = x \ \text{(linear)} \qquad \varphi = R^{\,x - 1}\ \text{(equal \%)} \qquad q = \frac{\varphi}{\sqrt{N + (1 - N)\varphi^2}} \qquad \frac{dq}{dx} = \frac{N}{[N + (1 - N)\varphi^2]^{3/2}}\,\frac{d\varphi}{dx} \qquad q_{min} = \frac{1/R}{\sqrt{N + (1 - N)/R^2}}\)

Variables

Symbol Meaning SI unit
\(\text{char}\) inherent characteristic –
\(x\) travel –
\(R\) inherent rangeability –
\(N\) valve authority –
\(\varphi\) inherent relative flow –
\(q\) installed relative flow –
\(dq/dx\) installed gain –
\(q_{min}\) installed flow at the least controllable opening –

Method and standards

Ideal inherent characteristics with a valve in series with a fixed-resistance system of constant total pressure drop.

Where it is used

  • Choosing valve trim.
  • Explaining poor control at low or high load.
  • Feedwater and spray control valves.

Common mistakes

  • Ignoring authority.
  • Oversized valves working near closed.
  • Confusing inherent and installed rangeability.

Assumptions and limits

  • Ideal characteristics; constant total system drop; turbulent flow.
  • The least controllable inherent flow is 1/R of the full flow for either characteristic.
  • The 0.25 authority warning is a common rule of thumb, not a standard limit.

References

  • IEC 60534-2-4 (inherent characteristics)

Questions and answers

What flows through an equal-% valve at 50 % open with R 50 and authority 0.3?

Inherent 14.1 % of full flow; installed 25.2 %, with gain 0.94.

What is valve authority?

Valve pressure drop fully open divided by the total system drop; low authority distorts the characteristic toward quick-opening.

When to choose equal percentage?

When most of the system drop is outside the valve: its installed curve becomes nearly linear.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.