Worked example
Example: 100 kW drive, 0.95 DPF, 40 % THD. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Displacement power factor (fundamental) | 95.000 % |
| Current total harmonic distortion | 40.000 % |
| Active power | 100.00 kW |
| Line voltage | 415.00 V |
Applying the formula below gives:
| Result | Value |
|---|---|
| Distortion factor | 0.92848 |
| True power factor | 0.88205 |
| Apparent power | 113.37 kVA |
| RMS line current | 157.72 A |
Open this example in the calculator and change any input.
Formula
\(DF = \frac{1}{\sqrt{1 + THD_I^2}}, \quad PF = \cos\phi_1\cdot DF, \quad S = \frac{P}{PF}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\cos\phi_1\) | Displacement power factor (fundamental) | - |
| \(THD_I\) | Current total harmonic distortion | - |
| \(P\) | Active power | W |
| \(V\) | Line voltage | V |
| \(DF\) | Distortion factor | - |
| \(PF\) | True power factor | - |
| \(S\) | Apparent power | VA |
| \(I_{rms}\) | RMS line current | A |
Method and standards
IEEE 1459 definitions.
Where it is used
- Drive and rectifier load studies.
- Explaining utility billing differences.
Common mistakes
- Using voltage THD.
- Applying capacitors to distorted loads.
Assumptions and limits
- Sinusoidal voltage.
References
- PF = cos φ₁ / √(1 + THD_I²) (IEEE 1459 definitions)
Questions and answers
Why is a drive's power factor low though its displacement factor is high?
Its current is distorted; harmonic current adds rms current and apparent power but no useful power.
Will capacitors fix it?
No: they only correct displacement factor and can make harmonic problems worse.
What do the defaults represent?
A 100 kW drive load with 0.95 displacement factor and 40 % current THD at 415 V.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.