True Power Factor with Harmonic Distortion

True power factor of a non-linear load as displacement factor times distortion factor from current THD, with apparent power and rms current.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 100 kW drive, 0.95 DPF, 40 % THDRectifier 0.97 DPF, 80 % THD

Results

Voltage assumed sinusoidal. Capacitors correct only displacement power factor; filters or active front ends are needed to improve the distortion factor.

Distortion factor0.78087
True power factor0.75744
Apparent power66.012kVA
RMS line current91.836A

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 100 kW drive, 0.95 DPF, 40 % THD. The inputs, in the units selected above:

InputValue
Displacement power factor (fundamental)95.000 %
Current total harmonic distortion40.000 %
Active power100.00 kW
Line voltage415.00 V

Applying the formula below gives:

ResultValue
Distortion factor0.92848
True power factor0.88205
Apparent power113.37 kVA
RMS line current157.72 A

Open this example in the calculator and change any input.

Formula

\(DF = \frac{1}{\sqrt{1 + THD_I^2}}, \quad PF = \cos\phi_1\cdot DF, \quad S = \frac{P}{PF}\)

Variables

Symbol Meaning SI unit
\(\cos\phi_1\) Displacement power factor (fundamental) -
\(THD_I\) Current total harmonic distortion -
\(P\) Active power W
\(V\) Line voltage V
\(DF\) Distortion factor -
\(PF\) True power factor -
\(S\) Apparent power VA
\(I_{rms}\) RMS line current A

Method and standards

IEEE 1459 definitions.

Where it is used

  • Drive and rectifier load studies.
  • Explaining utility billing differences.

Common mistakes

  • Using voltage THD.
  • Applying capacitors to distorted loads.

Assumptions and limits

  • Sinusoidal voltage.

References

  • PF = cos φ₁ / √(1 + THD_I²) (IEEE 1459 definitions)

Questions and answers

Why is a drive's power factor low though its displacement factor is high?

Its current is distorted; harmonic current adds rms current and apparent power but no useful power.

Will capacitors fix it?

No: they only correct displacement factor and can make harmonic problems worse.

What do the defaults represent?

A 100 kW drive load with 0.95 displacement factor and 40 % current THD at 415 V.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.