Transformer K-Factor and Derating from a Harmonic Spectrum

K-factor of a non-linear load from the per-unit harmonic currents of up to six orders, and the approximate transformer derating for a standard (K-1) transformer.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Six-pulse drive spectrumIT loads, strong 3rd

Results

K = ΣI_h²h²/ΣI_h². Derating I_max = √((1 + P_EC)/(1 + K·P_EC)) per unit of rated rms current (IEEE C57.110 approach with P_EC from the transformer maker; 0.05–0.15 for dry types).

Total rms current (pu)1.3013
K-factor6.9828
Current THD83.271%
Permissible load as share of rating78.063%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Six-pulse drive spectrum. The inputs, in the units selected above:

InputValue
Fundamental current (per unit)1.0000 -
3rd harmonic (pu)0.050000 -
5th (pu)0.35000 -
7th (pu)0.20000 -
11th (pu)0.080000 -
13th (pu)0.060000 -
Eddy-current loss share at rated load (pu of I²R)0.10000 -

Applying the formula below gives:

ResultValue
Total rms current (pu)1.0840
K-factor6.3215
Current THD41.833 %
Permissible load as share of rating82.095 %

Open this example in the calculator and change any input.

Formula

\(K = \frac{\sum I_h^2h^2}{\sum I_h^2}, \quad I_{max} = \sqrt{\frac{1 + P_{EC}}{1 + K\,P_{EC}}}\)

Variables

Symbol Meaning SI unit
\(I_1\) Fundamental current (per unit) -
\(I_3\) 3rd harmonic (pu) -
\(I_5\) 5th (pu) -
\(I_7\) 7th (pu) -
\(I_{11}\) 11th (pu) -
\(I_{13}\) 13th (pu) -
\(P_{EC}\) Eddy-current loss share at rated load (pu of I²R) -
\(I_{rms}\) Total rms current (pu) -
\(K\) K-factor -
\(THD_I\) Current THD -
\(I_{max}\) Permissible load as share of rating -

Method and standards

K-factor and derating.

Where it is used

  • Transformer selection for drive and IT loads.
  • Checking overheated transformers.

Common mistakes

  • Using voltage THD instead of current spectrum.
  • Ignoring other-stray losses for oil transformers.

Assumptions and limits

  • Only the winding eddy-current loss is scaled by K. IEEE C57.110 also scales the other stray losses (in structural parts and tank) with harmonic order to the power 0.8; for liquid-filled transformers these can be significant, so the derating here is optimistic for them.

  • Only the orders listed (up to the 13th) are counted; spectra with large higher-order content give a higher K than shown.

  • Listed orders only.

References

  • K-factor definition (UL 1561) and eddy-loss derating I_max = √((1 + P_EC)/(1 + K·P_EC)) (IEEE C57.110 approach)

Questions and answers

What is K-factor?

How much harmonics multiply winding eddy losses compared with sinusoidal current; K = 1 for a linear load, 4–13 for drive and IT loads.

Why do harmonics heat transformers?

Eddy losses rise with the square of frequency, so high-order harmonics heat windings far more than their share of current.

What do the defaults represent?

A six-pulse drive spectrum with 35 % 5th and 20 % 7th.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.