Worked example
Example: Six-pulse drive spectrum. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fundamental current (per unit) | 1.0000 - |
| 3rd harmonic (pu) | 0.050000 - |
| 5th (pu) | 0.35000 - |
| 7th (pu) | 0.20000 - |
| 11th (pu) | 0.080000 - |
| 13th (pu) | 0.060000 - |
| Eddy-current loss share at rated load (pu of I²R) | 0.10000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total rms current (pu) | 1.0840 |
| K-factor | 6.3215 |
| Current THD | 41.833 % |
| Permissible load as share of rating | 82.095 % |
Open this example in the calculator and change any input.
Formula
\(K = \frac{\sum I_h^2h^2}{\sum I_h^2}, \quad I_{max} = \sqrt{\frac{1 + P_{EC}}{1 + K\,P_{EC}}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_1\) | Fundamental current (per unit) | - |
| \(I_3\) | 3rd harmonic (pu) | - |
| \(I_5\) | 5th (pu) | - |
| \(I_7\) | 7th (pu) | - |
| \(I_{11}\) | 11th (pu) | - |
| \(I_{13}\) | 13th (pu) | - |
| \(P_{EC}\) | Eddy-current loss share at rated load (pu of I²R) | - |
| \(I_{rms}\) | Total rms current (pu) | - |
| \(K\) | K-factor | - |
| \(THD_I\) | Current THD | - |
| \(I_{max}\) | Permissible load as share of rating | - |
Method and standards
K-factor and derating.
Where it is used
- Transformer selection for drive and IT loads.
- Checking overheated transformers.
Common mistakes
- Using voltage THD instead of current spectrum.
- Ignoring other-stray losses for oil transformers.
Assumptions and limits
Only the winding eddy-current loss is scaled by K. IEEE C57.110 also scales the other stray losses (in structural parts and tank) with harmonic order to the power 0.8; for liquid-filled transformers these can be significant, so the derating here is optimistic for them.
Only the orders listed (up to the 13th) are counted; spectra with large higher-order content give a higher K than shown.
Listed orders only.
References
- K-factor definition (UL 1561) and eddy-loss derating I_max = √((1 + P_EC)/(1 + K·P_EC)) (IEEE C57.110 approach)
Questions and answers
What is K-factor?
How much harmonics multiply winding eddy losses compared with sinusoidal current; K = 1 for a linear load, 4–13 for drive and IT loads.
Why do harmonics heat transformers?
Eddy losses rise with the square of frequency, so high-order harmonics heat windings far more than their share of current.
What do the defaults represent?
A six-pulse drive spectrum with 35 % 5th and 20 % 7th.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.