Footing Size from Safe Bearing Capacity

Plan area and size of an isolated square or rectangular footing from the column load, the self-weight allowance and the safe bearing capacity of the soil.

Inputs

Examples: 1200 kN on 200 kPa, square800 kN on 150 kPa, L/B 1.5

Results

Round the sizes up to your detailing step; the structural design of the footing is separate.

Area required6.1333m²
Width2.0221m
Length3.0332m
Net upward soil pressure under service load P/(BL)130.43kPa

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1200 kN on 200 kPa, square. The inputs, in the units selected above:

InputValue
Column load (service)1,200.0 kN
Allowance for footing and soil weight10.000 %
Safe (allowable) bearing capacity200.00 kPa
Length to width ratio1.0000 -

Applying the formula below gives:

ResultValue
Area required6.6000 m²
Width2.5690 m
Length2.5690 m
Net upward soil pressure under service load P/(BL)181.82 kPa

Open this example in the calculator and change any input.

Formula

\(A = \frac{P(1 + k_{sw})}{q_a}, \quad B = \sqrt{\frac{A}{L/B}}\)

Variables

Symbol Meaning SI unit
\(P\) Column load (service) N
\(k_{sw}\) Allowance for footing and soil weight -
\(q_a\) Safe (allowable) bearing capacity Pa
\(L/B\) Length to width ratio -
\(A\) Area required m²
\(B\) Width m
\(L\) Length m
\(q_n\) Net upward soil pressure under service load P/(BL) (not the ultimate bearing capacity q_u) Pa

Method and standards

Area from allowable pressure.

Where it is used

  • Column and equipment footings.
  • Quick foundation estimates.

Common mistakes

  • Ultimate instead of safe bearing capacity.
  • Forgetting self-weight.

Assumptions and limits

  • Concentric load; service (unfactored) load. q_n is the net upward pressure for the footing's structural design under service load; limit-state design uses the factored load.

References

  • A = P(1 + k)/q_a (foundation design practice)

Questions and answers

1200 kN with 10 % self-weight on 200 kPa soil?

6.6 m²: a square of 2.57 m, say 2.6 m.

Why add self-weight?

The soil carries the footing and backfill too.

And the factored design?

The net upward pressure from the service load is the usual start; factor it per your code.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.