Process Condenser Duty: Desuperheat, Condense, Sub-Cool

Duty of a process condenser that desuperheats, condenses and sub-cools a vapour, from flow, specific heats and latent heat, with the cooling water flow.

Refinery and petrochemicalChemical and fertiliser

Inputs

Examples: Solvent overheadSaturated vapour, no sub-cooling

The constant-pressure specific heat c_p of the vapour (the symbol c_v here means vapour, not constant volume).

Results

Rate each zone separately: they have very different coefficients and temperature differences.

Desuperheating42.500kW
Condensing333.33kW
Sub-cooling17.500kW
Total duty393.33kW
Cooling water42.344t/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Solvent overhead. The inputs, in the units selected above:

InputValue
Vapour flow3,000.0 kg/h
Vapour specific heat at constant pressure1.7000 kJ/(kg·K)
Superheat to remove30.000 K
Latent heat at the condensing temperature400.00 kJ/kg
Liquid specific heat2.1000 kJ/(kg·K)
Sub-cooling10.000 K
Cooling water specific heat4.1800 kJ/(kg·K)
Cooling water temperature rise8.0000 K

Applying the formula below gives:

ResultValue
Desuperheating42.500 kW
Condensing333.33 kW
Sub-cooling17.500 kW
Total duty393.33 kW
Cooling water42.344 t/h

Open this example in the calculator and change any input.

Formula

\(\dot Q = \dot m\left[c_v \Delta T_{sh} + \lambda + c_l \Delta T_{sc}\right], \quad \dot m_w = \frac{\dot Q}{c_w \Delta T_w}\)

Variables

Symbol Meaning SI unit
\(\dot m\) Vapour flow kg/s
\(c_v\) Vapour specific heat at constant pressure J/(kg·K)
\(\Delta T_{sh}\) Superheat to remove K
\(\lambda\) Latent heat at the condensing temperature J/kg
\(c_l\) Liquid specific heat J/(kg·K)
\(\Delta T_{sc}\) Sub-cooling K
\(c_w\) Cooling water specific heat J/(kg·K)
\(\Delta T_w\) Cooling water temperature rise K
\(\dot Q_{sh}\) Desuperheating W
\(\dot Q_{c}\) Condensing W
\(\dot Q_{sc}\) Sub-cooling W
\(\dot Q\) Total duty W
\(\dot m_w\) Cooling water kg/s

Method and standards

Energy balance.

Where it is used

  • Column overhead and solvent condensers.
  • Cooling water planning.

Common mistakes

  • Latent heat at the wrong pressure.
  • One overall LMTD for all zones.

Assumptions and limits

  • Pure vapour.
  • c_v is the vapour's constant-pressure specific heat (v for vapour).

References

  • Energy balance by zones: sensible
  • latent
  • sensible

Questions and answers

3000 kg/h with 30 K superheat, 400 kJ/kg latent, 10 K sub-cool?

About 393 kW, mostly latent; 42.3 t/h of water at 8 K rise.

Why split into zones?

Each zone's LMTD and coefficient differ; one average misleads.

Non-condensables?

They lower the coefficient sharply; vent them.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.