Thermic Fluid Film Temperature (Dittus–Boelter)

Film (tube wall) temperature of a thermic fluid in a fired heater coil from bulk temperature, heat flux, tube size, velocity and fluid properties (Dittus–Boelter).

Refinery and petrochemicalChemical and fertiliserThermic fluid heatingFood, dairy and textileThermic fluid heater

Inputs

Examples: Bulk 290 °C, 40 kW/m², 50 mm tube, 2.5 m/sBulk 250 °C, 60 kW/m², 40 mm, 2 m/sBulk 300 °C, 30 kW/m², 60 mm, 3 m/sTherminol 55 at 290 °C bulk, 40 kW/m², 50 mm, 2.5 m/sTherminol VP-1 at 315 °C bulk, 60 kW/m², 40 mm, 2 m/s

Fluid properties (used when the fluid is "enter the properties")

Results

Compare the film temperature with the fluid maker's maximum film temperature.

Film (inside wall) temperature311.54°C
Film temperature rise above bulk11.536K
Film heat transfer coefficient2,600.6W/(m²·K)
Reynolds number360,000
Prandtl number10.516
Nusselt number1,642.5

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Bulk 290 °C, 40 kW/m², 50 mm tube, 2.5 m/s. The inputs, in the units selected above:

InputValue
Bulk fluid temperature290.00 °C
Heat flux at the tube inside wall40.000 kW/m²
Tube inside diameter50.000 mm
Fluid velocity in the tube2.5000 m/s
Thermic fluidEnter the properties below
Density of the fluid760.00 kg/m³
Specific heat of the fluid2.6000 kJ/(kg·K)
Thermal conductivity of the fluid0.10000 W/(m·K)
Kinematic viscosity of the fluid0.60000 cSt

Applying the formula below gives:

ResultValue
Film (inside wall) temperature307.98 °C
Film temperature rise above bulk17.977 K
Film heat transfer coefficient2,225.1 W/(m²·K)
Reynolds number208,333
Prandtl number11.856
Nusselt number1,112.5

Open this example in the calculator and change any input.

Formula

\(Re = \frac{v\,d_i}{\nu} \qquad Pr = \frac{\rho\,\nu\,c_p}{k} \qquad Nu = 0.023\,Re^{0.8}\,Pr^{0.4} \qquad h = \frac{Nu\,k}{d_i}\)

\(\Delta T_f = \frac{q''}{h} \qquad T_f = T_b + \Delta T_f\)

Variables

Symbol Meaning SI unit
\(T_b\) bulk fluid temperature K
\(q''\) heat flux at the inside wall W/m²
\(d_i\) tube inside diameter m
\(v\) fluid velocity m/s
\(\text{fluid}\) fluid chosen, or properties entered –
\(\rho\) density kg/m³
\(c_p\) specific heat J/(kg·K)
\(k\) thermal conductivity W/(m·K)
\(\nu\) kinematic viscosity m²/s
\(T_f\) film temperature K
\(\Delta T_f\) film rise above bulk K
\(h\) film coefficient W/(m²·K)
\(Re\) Reynolds number –
\(Pr\) Prandtl number –
\(Nu\) Nusselt number –

Method and standards

Dittus–Boelter correlation for fully developed turbulent flow in smooth tubes, with the Prandtl exponent 0.4 for a fluid being heated; fluid properties at the bulk temperature. Fluid properties: either typed in, or taken from the makers' published liquid tables for Therminol 55 (Eastman bulletin TF8994), Therminol VP-1 (Eastman bulletin TF9141), DOWTHERM A (Dow technical data sheet; no kinematic viscosity tabulated) and Therminol 66 (Eastman bulletin SFE-HTF-19853), interpolated linearly between the published points (viscosity linearly in its logarithm) and never extrapolated. More fluids will be added as their makers' tables are captured. With a tabulated fluid, the film temperature is checked against the maker's maximum film temperature (Therminol 55: 335 °C; Therminol VP-1: 430 °C; Therminol 66: 375 °C).

Where it is used

  • Checking heater coil design against the fluid's film temperature limit.
  • Setting minimum circulation flow.
  • Investigating fluid cracking and coil coking.

Common mistakes

  • Using the average heat flux where the radiant section peak is much higher.
  • Applying the correlation in laminar or transitional flow.
  • Using the cold-oil viscosity.

Assumptions and limits

  • Turbulent flow (Re above about 10 000), 0.6 < Pr < 160; uniform flux; properties at bulk temperature with no wall-viscosity correction (a source of error for viscous oils at high flux).
  • Below Re 10 000 no film temperature is shown, because Dittus–Boelter would under-predict it.
  • DOWTHERM A is not offered here because the maker publishes no viscosity table for it; choose "enter the properties" and type its viscosity.

References

  • Dittus–Boelter correlation (Dittus and Boelter 1930, as given by McAdams)

Questions and answers

What is the film temperature of a thermic fluid?

The temperature of the oil at the tube wall, above the bulk. With bulk at 290 °C, 40 kW/m² heat flux, 50 mm tubes and 2.5 m/s, the film coefficient is 2225 W/(m²·K) and the film runs 18 K hotter, at 308 °C.

Why does it matter?

Every fluid has a maximum film temperature; above it the oil cracks and cokes, fouling the coil and shortening fluid life. Keep the film below the maker's limit with margin.

How do I lower the film temperature?

Raise the velocity in the coil, lower the heat flux (larger heater or lower firing), or keep the bulk temperature lower.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.