Thermic Fluid Expansion Tank Volume

Expansion volume of a thermic fluid (hot oil) system from cold and hot densities and the expansion tank volume for the share of the tank you allow it to fill.

Refinery and petrochemicalChemical and fertiliserThermic fluid heatingFood, dairy and textileThermic fluid heaterTank and drum

Inputs

Examples: 10 m³ system, 870 kg/m³ cold, 700 hot, 60 % usable3 m³, 880, 740, 50 %25 m³, 860, 690, 65 %Therminol 55: 10 m³, filled at 30 °C, 300 °C max, 60 % usableTherminol VP-1: 5 m³, 20 to 320 °C, 60 %DOWTHERM A: 8 m³, 15 to 305 °C, 55 %

Space between the cold level and the high-level alarm, as a share of the tank volume; your design rule or code sets it.

Fluid properties (used when the fluid is "enter the properties")

Results

Expansion tank volume9.4760m³
Expansion of the fluid6.1594m³
Volume expansion, share of cold volume24.638%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 m³ system, 870 kg/m³ cold, 700 hot, 60 % usable. The inputs, in the units selected above:

InputValue
System fluid volume when cold (heater, pipes, users)10.000 m³
Thermic fluidEnter the properties below
Cold filling temperature (for the fluid tables)30.000 °C
Maximum operating temperature (for the fluid tables)300.00 °C
Density at the cold filling temperature870.00 kg/m³
Density at the maximum operating temperature700.00 kg/m³
Share of the tank the expansion may fill60.000 %

Applying the formula below gives:

ResultValue
Expansion tank volume4.0476 m³
Expansion of the fluid2.4286 m³
Volume expansion, share of cold volume24.286 %

Open this example in the calculator and change any input.

Formula

\(e = \frac{\rho_c}{\rho_h} - 1 \qquad \Delta V = V\,e \qquad V_t = \frac{\Delta V}{f}\)

Variables

Symbol Meaning SI unit
\(V\) system fluid volume when cold m³
\(\text{fluid}\) fluid chosen, or properties entered –
\(T_c\) cold filling temperature (tabulated fluids) K
\(T_h\) maximum operating temperature (tabulated fluids) K
\(\rho_c\) density at filling temperature kg/m³
\(\rho_h\) density at maximum operating temperature kg/m³
\(f\) share of the tank the expansion may fill –
\(V_t\) expansion tank volume m³
\(\Delta V\) fluid expansion m³
\(e\) volume expansion ratio –

Method and standards

Mass conservation: the fluid's mass is fixed, so its volume grows as density falls. Densities at the cold and hot temperatures. Fluid properties: either typed in, or taken from the makers' published liquid tables for Therminol 55 (Eastman bulletin TF8994), Therminol VP-1 (Eastman bulletin TF9141), DOWTHERM A (Dow technical data sheet; no kinematic viscosity tabulated) and Therminol 66 (Eastman bulletin SFE-HTF-19853), interpolated linearly between the published points (viscosity linearly in its logarithm) and never extrapolated. More fluids will be added as their makers' tables are captured.

Where it is used

  • Sizing expansion tanks of hot oil systems.
  • Checking an existing tank after the system is extended.
  • Setting tank level alarms.

Common mistakes

  • Using the heater volume only and forgetting pipes and users.
  • Using a linear expansion coefficient over a wide temperature range.
  • Leaving no room for the low-level reserve.

Assumptions and limits

  • Whole system at the maximum temperature; no fluid loss.
  • The tank volume covers the expansion only; the low-level reserve and vapour space must fit in the share f you choose (no minimum reserve is checked).
  • With a tabulated fluid the temperatures are used and the typed densities ignored; with "enter the properties" the densities are used and the temperatures ignored.

References

  • Mass conservation (volume change from density change)

Questions and answers

How much does thermic fluid expand?

By the ratio of its cold to hot density. A fluid at 870 kg/m³ cold and 700 kg/m³ hot expands 24.3 %; a 10 m³ system grows by 2.43 m³ and, using 60 % of the tank, needs a 4.05 m³ expansion tank.

What share of the tank can the expansion use?

The space between the cold filling level and the high-level alarm; the rest is the low-level reserve and vapour space. Your design rule or applicable code sets it; this calculator takes it as an input.

Should the tank be hot?

No. The expansion tank is kept cool (often by a cold seal leg) to slow oxidation of the oil in contact with air.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.