Worked example
Example: 15 kg/s, two 2½-in. passes of 250 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fluid flow | 54,000 kg/h |
| Fluid density at mean temperature | 780.00 kg/m³ |
| Fluid dynamic viscosity at mean temperature | 0.45000 cP |
| Coil inside diameter | 62.700 mm |
| Parallel coil passes | 2.0000 - |
| Developed length per pass | 250.00 m |
| Return bends per pass | 40.000 - |
| Loss coefficient per bend | 0.30000 - |
| Roughness | 0.045000 mm |
| Rest of the circuit (users, piping) | 150.00 kPa |
| Pump efficiency | 60.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Velocity in the coil | 3.1142 m/s |
| Reynolds number | 338,448 |
| Darcy friction factor | 0.019221 |
| Coil pressure drop | 335.25 kPa |
| Total pump differential | 485.25 kPa |
| Pump shaft power | 15.553 kW |
Open this example in the calculator and change any input.
Formula
\(V = \frac{\dot m}{n_p\rho\pi d_i^2/4}, \quad \Delta p_{coil} = \left(f_D\frac{L}{d_i} + n_bK_b\right)\frac{\rho V^2}{2}, \quad P = \frac{\dot m}{\rho}\frac{\Delta p}{\eta}\)
\(Re = \frac{\rho V d_i}{\mu}, \quad f_D = \text{Colebrook}(Re, \varepsilon/d_i)\ (64/Re\ \text{laminar}), \quad \Delta p = \Delta p_{coil} + \Delta p_{ext}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | Fluid flow | kg/s |
| \(\rho\) | Fluid density at mean temperature | kg/m³ |
| \(\mu\) | Fluid dynamic viscosity at mean temperature | Pa·s |
| \(d_i\) | Coil inside diameter | m |
| \(n_p\) | Parallel coil passes | - |
| \(L\) | Developed length per pass | m |
| \(n_b\) | Return bends per pass | - |
| \(K_b\) | Loss coefficient per bend | - |
| \(\varepsilon\) | Roughness | m |
| \(\Delta p_{ext}\) | Rest of the circuit (users, piping) | Pa |
| \(\eta\) | Pump efficiency | - |
| \(V\) | Velocity in the coil | m/s |
| \(Re\) | Reynolds number | - |
| \(f_D\) | Darcy friction factor | - |
| \(\Delta p_{coil}\) | Coil pressure drop | Pa |
| \(\Delta p\) | Total pump differential | Pa |
| \(P\) | Pump shaft power | W |
Method and standards
Darcy–Weisbach friction with the Colebrook friction factor from FireCAD's engine, plus a fixed loss coefficient per return bend; the pump power is the volume flow times the total differential over the pump efficiency.
Where it is used
- Heater and pump selection.
- Checking coil velocity after a fluid change.
Common mistakes
- Using cold-oil viscosity at operating temperature.
- Ignoring parallel-pass maldistribution.
Assumptions and limits
- Single phase; even flow per pass.
- The bend loss is a fixed K per bend, independent of Reynolds number and bend radius. If the developed length L already includes the bends, do not count their friction twice.
References
- Darcy–Weisbach with Colebrook (FireCAD engine) and bend losses (definitions)
Questions and answers
Why such high velocities?
Hot oil has a low film coefficient; 2–3.5 m/s in fired coils keeps the film temperature below the fluid's limit.
Where do properties come from?
The thermic fluid calculators give density and kinematic viscosity (cSt) of common fluids at temperature. This page takes dynamic viscosity (cP): multiply cSt by the density in g/cm³.
What do the defaults give?
15 kg/s in two 2½-in. passes of 250 m: about 3.1 m/s, coil drop about 3.4 bar plus 1.5 bar for the circuit, roughly 16 kW of pump power.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.