FireCADCalc

Thermic Fluid Heater Coil Pressure Drop and Pump Power

Velocity, Reynolds number, pressure drop and pump power of thermic fluid in a heater coil and circuit, from fluid properties, coil size, length and bends.

Refinery and petrochemicalChemical and fertiliserThermic fluid heatingPulp and paperFood, dairy and textile

Inputs

Examples: 15 kg/s, two 2½-in. passes of 250 mSmall heater 8 kg/s, one 2-in. pass

Dynamic viscosity in cP (mPa·s). Fluid tables usually give kinematic viscosity in cSt: multiply cSt by the density in g/cm³ (e.g. 0.6 cSt × 0.76 = 0.46 cP).

Results

Velocity in the coil3.1142m/s
Reynolds number338,448
Darcy friction factor0.019221
Coil pressure drop335.25kPa
Total pump differential485.25kPa
Pump shaft power15.553kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 15 kg/s, two 2½-in. passes of 250 m. The inputs, in the units selected above:

InputValue
Fluid flow54,000 kg/h
Fluid density at mean temperature780.00 kg/m³
Fluid dynamic viscosity at mean temperature0.45000 cP
Coil inside diameter62.700 mm
Parallel coil passes2.0000 -
Developed length per pass250.00 m
Return bends per pass40.000 -
Loss coefficient per bend0.30000 -
Roughness0.045000 mm
Rest of the circuit (users, piping)150.00 kPa
Pump efficiency60.000 %

Applying the formula below gives:

ResultValue
Velocity in the coil3.1142 m/s
Reynolds number338,448
Darcy friction factor0.019221
Coil pressure drop335.25 kPa
Total pump differential485.25 kPa
Pump shaft power15.553 kW

Open this example in the calculator and change any input.

Formula

\(V = \frac{\dot m}{n_p\rho\pi d_i^2/4}, \quad \Delta p_{coil} = \left(f_D\frac{L}{d_i} + n_bK_b\right)\frac{\rho V^2}{2}, \quad P = \frac{\dot m}{\rho}\frac{\Delta p}{\eta}\)

\(Re = \frac{\rho V d_i}{\mu}, \quad f_D = \text{Colebrook}(Re, \varepsilon/d_i)\ (64/Re\ \text{laminar}), \quad \Delta p = \Delta p_{coil} + \Delta p_{ext}\)

Variables

Symbol Meaning SI unit
\(\dot m\) Fluid flow kg/s
\(\rho\) Fluid density at mean temperature kg/m³
\(\mu\) Fluid dynamic viscosity at mean temperature Pa·s
\(d_i\) Coil inside diameter m
\(n_p\) Parallel coil passes -
\(L\) Developed length per pass m
\(n_b\) Return bends per pass -
\(K_b\) Loss coefficient per bend -
\(\varepsilon\) Roughness m
\(\Delta p_{ext}\) Rest of the circuit (users, piping) Pa
\(\eta\) Pump efficiency -
\(V\) Velocity in the coil m/s
\(Re\) Reynolds number -
\(f_D\) Darcy friction factor -
\(\Delta p_{coil}\) Coil pressure drop Pa
\(\Delta p\) Total pump differential Pa
\(P\) Pump shaft power W

Method and standards

Darcy–Weisbach friction with the Colebrook friction factor from FireCAD's engine, plus a fixed loss coefficient per return bend; the pump power is the volume flow times the total differential over the pump efficiency.

Where it is used

  • Heater and pump selection.
  • Checking coil velocity after a fluid change.

Common mistakes

  • Using cold-oil viscosity at operating temperature.
  • Ignoring parallel-pass maldistribution.

Assumptions and limits

  • Single phase; even flow per pass.
  • The bend loss is a fixed K per bend, independent of Reynolds number and bend radius. If the developed length L already includes the bends, do not count their friction twice.

References

  • Darcy–Weisbach with Colebrook (FireCAD engine) and bend losses (definitions)

Questions and answers

Why such high velocities?

Hot oil has a low film coefficient; 2–3.5 m/s in fired coils keeps the film temperature below the fluid's limit.

Where do properties come from?

The thermic fluid calculators give density and kinematic viscosity (cSt) of common fluids at temperature. This page takes dynamic viscosity (cP): multiply cSt by the density in g/cm³.

What do the defaults give?

15 kg/s in two 2½-in. passes of 250 m: about 3.1 m/s, coil drop about 3.4 bar plus 1.5 bar for the circuit, roughly 16 kW of pump power.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.