FireCADCalc

Storage Tank Wind Overturning, Sliding and Anchor Load

Wind force, overturning moment, stability and sliding factors of safety of an empty vertical tank, and the anchor bolt tension needed.

Inputs

Examples: Illustrative empty 12 x 14 m tankTall slender 6 x 15 mSquat 30 x 12 m

Accepted: 1 to 120 m
Accepted: 1 to 40 m
Accepted: 0.1 to 5,000 t
Accepted: 5 to 90 m/s
Accepted: 0.3 to 1.5
Accepted: 0.9 to 1.4 kg/m³
Accepted: 0.1 to 1
Accepted: 4 to 200

Results

F = ½ρv²C_f·DH at mid-height; overturning about the base edge resisted by the empty weight at D/2. Anchor bolt tension 4M/(nD) − W/n on the bolt circle (taken as D). Wind speeds and factors with height, gusts and code safety factors come from your wind code.

Wind pressure1.2403kPa
Wind force78.140kN
Overturning moment586.05kN·m
Overturning factor of safety0.60241
Sliding factor of safety0.60241
Anchor bolt tension (each)22.752kN

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative empty 12 x 14 m tank. The inputs, in the units selected above:

InputValue
Tank diameter12.000 m
Tank height14.000 m
Empty mass (shell, roof, bottom)45.000 t
Design wind speed45.000 m/s
Force coefficient0.70000 -
Air density1.2250 kg/m³
Base friction coefficient0.40000 -
Anchor bolts24.000 -

Applying the formula below gives:

ResultValue
Wind pressure1.2403 kPa
Wind force145.86 kN
Overturning moment1,021.0 kN·m
Overturning factor of safety2.5933
Sliding factor of safety1.2102
Anchor bolt tension (each)0 kN

Open this example in the calculator and change any input.

Formula

\(F = \tfrac12\rho v^2C_fDH, \quad FS_o = \frac{mgD/2}{FH/2}, \quad T_b = \frac{4M_o}{n_bD} - \frac{mg}{n_b}\)

Variables

Symbol Meaning SI unit
\(D\) Tank diameter m
\(H\) Tank height m
\(m\) Empty mass (shell, roof, bottom) kg
\(v\) Design wind speed m/s
\(C_f\) Force coefficient -
\(\rho\) Air density kg/m³
\(\mu\) Base friction coefficient -
\(n_b\) Anchor bolts -
\(q\) Wind pressure Pa
\(F\) Wind force N
\(M_o\) Overturning moment N·m
\(FS_o\) Overturning factor of safety -
\(FS_s\) Sliding factor of safety -
\(T_b\) Anchor bolt tension (each) N

Method and standards

Tank stability.

Where it is used

  • Tank anchoring design.
  • Construction stage checks.

Common mistakes

  • Using the full tank weight.
  • Ignoring internal vacuum or pressure uplift.

Assumptions and limits

  • Uniform wind on the projected area; rigid tank.

References

  • Rigid-body stability of a vertical tank under wind
  • Megyesy
  • Pressure Vessel Handbook (Pressure Vessel Publishing)

Questions and answers

Why check the tank empty?

An empty tank is lightest, so its resistance to overturning and sliding is smallest.

When are anchors needed?

When the overturning factor of safety drops below about 1.5, typically tall, slender, light tanks.

What do the defaults represent?

An illustrative empty 12 m diameter, 14 m tall tank weighing 45 t in a 45 m/s wind, 24 anchor bolts.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.