Worked example
Example: Speed 980 to 740 rpm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Volume flow | 72,000 m³/h |
| Pressure rise | 305.91 mmWC |
| Shaft power | 75.000 kW |
| Speed | 980.00 rpm |
| Gas density | 1.2000 kg/m³ |
| New speed | 740.00 rpm |
| Wheel diameter ratio (1 = same fan) | 1.0000 - |
| New gas density | 1.2000 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| New volume flow | 54,367 m³/h |
| New pressure rise | 174.43 mmWC |
| New shaft power | 32.291 kW |
| Speed ratio | 0.75510 |
| Density ratio | 1.0000 |
Open this example in the calculator and change any input.
Formula
\(\frac{\dot V_2}{\dot V_1} = \frac{N_2}{N_1}\left(\frac{D_2}{D_1}\right)^3 \qquad \frac{\Delta p_2}{\Delta p_1} = \frac{\rho_2}{\rho_1}\left(\frac{N_2}{N_1}\right)^2\left(\frac{D_2}{D_1}\right)^2 \qquad \frac{P_2}{P_1} = \frac{\rho_2}{\rho_1}\left(\frac{N_2}{N_1}\right)^3\left(\frac{D_2}{D_1}\right)^5\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V_1\) | known volume flow | m³/s |
| \(\Delta p_1\) | known pressure rise | Pa |
| \(P_1\) | known shaft power | W |
| \(N_1\) | known speed | 1/s |
| \(\rho_1\) | known gas density | kg/m³ |
| \(N_2\) | new speed | 1/s |
| \(D_2/D_1\) | wheel diameter ratio of geometrically similar fans | – |
| \(\rho_2\) | new gas density | kg/m³ |
| \(\dot V_2\) | new volume flow | m³/s |
| \(\Delta p_2\) | new pressure rise | Pa |
| \(P_2\) | new shaft power | W |
| \(N_2/N_1\) | speed ratio | – |
| \(\rho_2/\rho_1\) | density ratio | – |
Method and standards
The fan laws of AMCA Publication 99 and the similarity rules of ISO 5801, for geometrically similar fans at the same point of rating (same efficiency).
Where it is used
- Predicting fan flow, pressure and power after speed changes.
- VFD and inlet guide vane energy studies.
- Correcting fan tests to design conditions.
Common mistakes
- Ignoring density changes with temperature.
- Applying the laws across very different speeds where efficiency changes.
- Mixing static and total pressure.
Assumptions and limits
- The fan stays at the same point of its curve: the system resistance must follow Δp ∝ ρ·V̇². A system with a fixed static component does not follow the laws along its own curve.
- Efficiency is taken as constant; this holds for moderate changes (about −50 % to +20 % speed).
- The diameter law applies to geometrically similar fans, not to a trimmed wheel in the same casing.
- Compressibility and Reynolds-number effects are neglected.
References
- AMCA Publication 99 (fan laws)
- ISO 5801 (similarity)
Questions and answers
What are the three fan laws?
For one fan, flow varies with speed, pressure with speed squared and power with speed cubed. Slowing a fan from 980 to 740 rpm cuts flow to 75.5 %, pressure to 57 % and power to 43 %.
How does gas temperature affect a fan?
At constant speed the volume flow stays the same, while pressure and power fall in proportion to density. An ID fan handling gas at 200 °C instead of 150 °C develops 10.6 % less pressure and absorbs 10.6 % less power.
Why size the motor of an ID fan for cold gas?
At a cold start the gas is denser, so at the same speed and damper position the fan absorbs more power than at design temperature.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.